Fitting flexible connectors
If flexible connectors have been supplied separately, install them once the AHU units have been set up and assem-
bled. Depending on the AHU construction variant the flexible connectors have to be attached to the AHU casing, to
the base frame or to a multileaf damper.
Fig. 15: Flexible connector
Item
Meaning
Part no.
①
Flexible connector
②
Thread forming pan head screw
M852AC6
③
Ground cable
④
Schnorr washer
A00000055655
⑤
Secure all screw joints.
By others
1.
Fix the flexible connector ( Fig. 15 /1) with screws ( Fig. 15 /2) to the AHU.
2.
Fix one eye of the ground cable ( Fig. 15 /3) with a screw ( Fig. 15 /2) and a Schnorr washer ( Fig. 15 /4) to the
panel of the AHU. Fix the other eye of the ground cable to the duct (conductive) and secure it ( Fig. 15 /5).