E X P L O S I O N P R O O F
!
!
ExBin- FR...
U
o
= 7.14 V
I
o
= 8 mA
P
o
= 15 mW
C
i
→
0
L
i
→
0
IIC IIB IIA
L
o
5 mH 10 mH 20 mH
C
o
1.5
μ
F 6.7
μ
F 8.6
μ
F
!
ExBin-FR...
SB 1.0
PA
5
6
1
2
PE
24 VAC/DC
+
~
−
~
SW
-IN (GND)
SW
-C
h1
www.schischek.com
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]
ExBin-FR_en
V01 – 9-Nov-2016
Electrical connection
Relais output
250 V AC
/ 0.1 A
220 V DC
/ 0.1 A
30 V AC/DC / 0.5 A
Supply *
24 V AC/DC ± 20 %
* electrical wiring see diagram
Installation
Hazardous (classified)
locations
Nonhazardous
locations
▪ Do not crack the capillary,
note capillary’s bending radius
All frost protection thermostats require a 24 VAC/DC power supply. The electrical wiring
must be realized via the integrated Ex-e terminal box acc. to ATEX. The terminals’ type of
protection is “Increased safety Ex-e”.
Attention: Before opening the terminal box cover, the supply voltage must be shut off !
The supply has to be connected at terminals 1 (
−
/~) and 2 (+/~).
At different relay and supply voltages (24 VAC/DC)
the cable installation must be considered
(see “Information for Installation”) !
Relay output
250 VAC / 0.1 A – 220 VDC / 0.1 A
30 VAC/DC / 0.5 A
Function relay:
Open:
Temperature is below
the setpoint
Closed:
Temperatur is above
the setpoint (normal)
Control elements with status indication
Intrinsically safe parameters (IS) – Internal contact
green
red
Normal temperature
range for frost
protection thermostat
Rotary control for
setpoint setting
Temperature scale
Fixing screw
Notice:
Retain rotary control
LEDs for
status
indication
A. Installation, commissioning, maintenance
All national and international standards, rules and regulations must be complied with.
Certified apparatus must be installed in accordance with manufacturer instructions.
If the equipment is used in a manner not specified by the manufacturer, the safety protec-
tion provided by the equipment may be impaired. For electrical installations design,
selection and erection, EN/IEC 60079-14 can be used.
Attention: Apply all Ex rules and regulation before opening the internal terminal
box. Do not open cover when circuits are live!
Draw the wiring cables through the cable glands. For connection use the internal Ex-e
approved terminal box and connect equipotential bonding.
After connection install the cables in a fixed position and protect them against mechanical
and thermical damage. Close all openings and ensure IP protection (min. IP66).
Avoid temperature transfer and ensure not to exceed max. ambient temperature! For
outdoor installation a protective shield against sun, rain and snow should be applied.
Sensors are maintenance free. An annual inspection is recommended. For electrical
installations inspection and maintenance, EN/IEC 60079-17 can be used.
Clean with damp cloth only.
Ex sensors must not be opened and repaired by the end user.
B. Long cabling
We recommend using shielded signal wires and to connect one end of the shield to the
...Bin-... terminal box.
C. Separate ground wires
For supply and signal wires use separate grounds.
D. Relay output
Wires for safety extra-low voltage must be installed separately from other circuits. At
24 VAC/DC only supply and signal wires are permitted in one cable, in all other cases
use separate or double isolated cables. An over-current protection fuse < 10 A has to
be provided by the installer.
3 / 3