BA-CFD-RLM-ATEX 4.0
– 05/2019
English
EN-19/24
10.4 Maintenance recommendations for Fans RLM-ATEX
Table 10-1: Maintenance
recommendation
Conduct test run if applicable (see Chapter 8.4).
Document inspection intervals observed.
Description
quarterly cyclic on demand
1.0 Fan
1.1
Check deposit, damages, corrosion and fixing
X
1.2
Check impeller for damage and unbalancing, vibration check
X
1.3
Check the axial and radial gap
X
1.4
Check flexible connections for tightness
X
1.5
Check correct function of AVM
X
1.6
Check correct function of safety devices (guards)
X
1.7
Check condensate water drain
X
1.8
Clean entire unit in order to keep all elements in best working conditions
X
1.9
Check rotational sense of impeller (for all speeds)
X
2.0
Check fan function and its readiness for immediate start up
X
2.1 Motor
2.2
Visual control for dirt, damages, corrosion and correct fixing
X
2.3
Check rotational sense
X
2.4
Check bearing noise
X
2.5
Lubricate bearing (where bearings are re-lubricable)
X
2.6
Check correct function of safety devices (guards)
X
2.7
Check tight electrical connections on tight fixing
X
2.8
Clean entire unit in order to keep all elements in best working conditions
X
Содержание X-CUBE Ex