BA-CFD-RLM-ATEX 4.0
– 05/2019
English
EN-12/24
Impeller
Inlet cone
6.4. Storage of Centrifugal Fan
CAUTION
Risk of corrosion!
Store the fan in its packaging adding any other protection dictated by its
storage environment
Store centrifugal fan in a well-ventilated room only at normal
temperatures and in a non-corrosive atmosphere
Store centrifugal fan in conditions registering less than 70 % atmospheric
humidity (non-condensing)
Adhere to max. permissible temperature of -20°C to +40°C
7.
Installation
7.1. Safety Instructions for Installation
Observe the safety instructions and preventive measures in Chapter 4
and the relevant legal requirements.
CAUTION
The ATEX- fan system supplied by Nicotra Gebhardt must not be
modified in any way! Its operation is exclusively permitted in it’s state
as originally supplied and within the LIMITS SPECIFIED. (Respect
catalogue- and type plate data).
7.1.1. Installation
notes
In order to achieve a sufficient motor cooling, care has to be taken that the
fan at motor side is keeping a minimum clearance (L1) to the next wall. For
disclosures on L1 refer to the motor operating instructions.
Figure 7-1:
Clearance
RLM E3: only vertical
installation, with air
direction from bottom to
top, permissible.
Minimum distance
determined by motor
protection cover.
7.2. Preparation to Installation
The place of installation must be suitable for the fan in terms of its
category, condition, ambient temperature and environmental media.
The base must be level and have sufficient load-bearing capacity.
1.
Unpack centrifugal fan carefully.
2.
Unfasten or dismantle transport locks
3.
Packing material to be fully removed and disposed.
4.
Check gaps as per 7.4.