E X P L O S I O N P R O O F
ExMax - ...
ExMax - ... - F
ExMax - ... - S
ExMax - ... - SF
ExMax - ... - CTM
www.schischek.com
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]
ExMax-M-3P_en
V02 – 20-Apr-2016
Subject to change!
Compact. Easy installation. Universal. Cost effective. Safe.
Product views and applications
Description
Highlights
Safety damper
Ball valve
Throttle valve
Electrical, explosion proof rotary actuators
On-off / 3-pos. control mode, 24…240 VAC/DC, 95° angle of rotation incl. 5° pretension
50 / 75 – 100 – 150 Nm without and 30 – 50 – 60 Nm with safety operation (spring return)
ATEX tested in acc. with directive 2014/34/EU for zone 1, 2, 21, 22
Type
Torque
Supply
Motor running time
Spring return
Control mode
Feedback
Wiring diagram
ExMax- 50.75
50 / 75 Nm
24...240 VAC/DC
40 / 60 / 90 / 120 / 150 s/90°
–
On-off, 3-pos.
–
SB 1.0
ExMax- 100
100 Nm
24...240 VAC/DC
40 / 60 / 90 / 120 / 150 s/90°
–
On-off, 3-pos.
–
SB 1.0
ExMax- 150
150 Nm
24...240 VAC/DC
40 / 60 / 90 / 120 s/90°
–
On-off, 3-pos.
–
SB 1.0
ExMax- 30 - F
30 Nm
24...240 VAC/DC
40 / 60 / 90 / 120 / 150 s/90°
~ 20 s/90°
On-off, 3-pos.
–
SB 2.2 + 2.3
ExMax- 50 - F
50 Nm
24...240 VAC/DC
40 / 60 / 90 / 120 / 150 s/90°
~ 20 s/90°
On-off, 3-pos.
–
SB 2.2 + 2.3
ExMax- 60 - F
60 Nm
24...240 VAC/DC
40 / 60 / 90 / 120 s/90°
~ 20 s/90°
On-off, 3-pos.
–
SB 2.2 + 2.3
ExMax- ... - S/SF Types as above with 2 integral, potential free auxiliary switches, 5° and 85° angle of rotation
2 × limit switches SB 3.0
ExMax- ... - CTM Types as above with aluminium housing and seawater resistant coating (cable glands brass nickel-plated)
ExMax
¼ turn actuators – size M
►
For all type of gas, mists, vapours and dust for use in zone 1, 2, 21 and 22
►
Universal supply unit from 24…240 VAC/DC
►
Different motor running times 40–60–90–120–150 s/90°, adjustable on site
►
Spring return running time ~ 20 s/90°
►
On-off and 3-pos. control with or without spring return function
►
30–50–60–75–100–150 Nm actuators in the same housing size
►
100 % overload protected
►
Compact design and small dimension (L × W × H = 288 × 149 × 116 mm)
►
Direct coupling to the damper shaft with double square connection 16 × 16 mm
►
95° angle of rotation inclusive 5° pretension
►
Robust aluminium housing (optional with seawater resistant coating)
►
IP66 protection
►
Simple manual override in preparation for comfortable manual override
►
Gear made of stainless steel and sinter metal
►
Weight only ~ 9,5 kg
►
Integral heater for ambient temperatures down to −40 °C
►
Integral safety temperature sensor
►
Integral equipment for manual adjustment (push button, lamp, switch)
►
Preparation for adaptable and adjustable auxiliary switches type ...Switch
►
Wide range of accessories
The ExMax actuators are a revolution for safety, control and shut-off
dampers, ball valves, throttle valves and other motorized applications for
HVAC systems in chemical, pharmaceutical, industrial and offshore/onshore
plants, for use in Ex-areas zone 1, 2 (gas) and zone 21, 22 (dust).
Highest protection class (ATEX) and IP66 protection, small dimensions,
only 9,5 kg weight, universal functions and technical data, an integrated
heater and an optional stainless steel housing guarantee safe operation
even under difficult environmental conditions. High quality brushless
motors guarantee long life.
All actuators are programmable and adjustable on site. Special tools or
equipment are not required. Motor running times and torques are selectable
or adjustable on site. The integrated universal power supply is self
adaptable to input voltages in the range of 24...240 VAC/DC. The actuators
are 100 % overload protected.
...Max-...F actuators are equipped with spring return fail safe function.
Standard shaft connection is a double square direct coupling with
16 × 16 mm.
Different accessories are available to adapt auxiliary switches, terminal
boxes or adaptions for ball valves and throttle valves and other armatures.
1 / 4
Содержание X-CUBE Ex
Страница 60: ...Appendix Appendix Air handling unit X CUBE Ex 60...
Страница 159: ...Supplier documents Air handling unit X CUBE Ex 159...