Analog inputs for 4-cool applications
CNT-SVX12C-EN
33
Analog inputs for 4-cool applications
The Tracer ZN517 controller has five analog inputs. Table 13 describes
the function of each input for 4-cool applications. Each function is
explained in the succeeding paragraphs. For an explanation of the diag-
nostics generated by each analog input, see “Table of diagnostics” on
page 79. For more information about how the controller operates, see
Chapter 6, “Sequence of operations for the 4-cool configuration”.
AI1: Universal 4–20 mA
The AI1 analog input can be configured in one of the three ways shown in
Table 14.
If this input is not needed for an application, configure it as Not Used.
This disables the generation of diagnostics.
For the generic input configuration, a 4–20 mA sensor must be hard-
wired to the AI1 terminal. (Wiring is dependent on the specific applica-
tion.) The sensor communicates a value of 0–100% to the BAS. This con-
figuration has no direct effect on Tracer ZN517 operation.
Table 13. Analog inputs for 4-cool applications
Analog input
terminal label
Function
AI1
Universal analog input
AI2
Outdoor air temperature
DAT
Discharge air temperature
ZN
Zone temperature (required)
SET
Temperature setpoint
Note:
Use a GND terminal as the common ground for all zone sensor
analog inputs. See Figure 9 on page 29.
Table 14. AI1 configuration options and associated measurement
ranges
Configuration
Measurement range
Generic 4–20 mA input
0–100%
(4 mA=0%; 20 mA=100%)
CO
2
measurement
0–2000 ppm
(4 mA=0 ppm; 20 mA=2000 ppm)
Relative humidity (RH) measurement
0–100%
(4 mA=0% RH; 20 mA=100% RH)
Note:
AI1 is polarity sensitive.
Содержание Tracer ZN517
Страница 1: ...CNT SVX12C EN Installation and Operation Tracer ZN517 Unitary Controller...
Страница 2: ......
Страница 3: ...Installation and Operation Tracer ZN517 Unitary Controller CNT SVX12C EN April 2005...
Страница 4: ......
Страница 12: ...Table of contents vi CNT SVX12C EN...
Страница 38: ...Chapter 4 Sequence of operations for the 2 heat 2 cool configuration 26 CNT SVX12C EN...
Страница 56: ...Chapter 6 Sequence of operations for the 4 cool configuration 44 CNT SVX12C EN...
Страница 92: ...Chapter 10 Status indicators for operation and communication 80 CNT SVX12C EN...
Страница 104: ...Chapter 12 Troubleshooting 92 CNT SVX12C EN...
Страница 110: ...Index 98 CNT SVX12C EN...