Chapter 1 Overview and specifications
2
CNT-SVX12C-EN
Metal-cover model dimensions
For complete dimensional drawing, see Figure 2 on page 3.
•
Height: 9.0 in (25 mm)
•
Width: 10.37in. (263 mm)
•
Depth: 2.25 in. (58 mm)
Clearances
For wiring, ventilation, and maintenance, provide the following minimum
clearances for the module:
Plastic-cover model
(see Figure 1 on page 3)
•
Front: 4.0 in. (102 mm)
•
Each side: 1.0 in. (25 mm)
•
Top and bottom: 4.0 in. (102 mm)
Metal-cover model
(see Figure 2 on page 3)
•
Front: 24.0 in. (610 mm)
•
Each side: 2.0 in. (51 mm)
•
Top and bottom: 1.0 in. (25 mm)
Power
The transformer must meet the following minimum requirements for the
controller and its output devices:
•
19–30 Vac (24 Vac nominal)
•
50/60 Hz
•
9 VA and 12 VA maximum per binary output utilized
Operating environment
Operate a Tracer ZN517 unitary controller in an indoor environment that
meets the following requirements:
•
Temperature: From –40°F to 160°F (–40°C to 70°C)
•
Relative humidity: From 5–90%, noncondensing
Содержание Tracer ZN517
Страница 1: ...CNT SVX12C EN Installation and Operation Tracer ZN517 Unitary Controller...
Страница 2: ......
Страница 3: ...Installation and Operation Tracer ZN517 Unitary Controller CNT SVX12C EN April 2005...
Страница 4: ......
Страница 12: ...Table of contents vi CNT SVX12C EN...
Страница 38: ...Chapter 4 Sequence of operations for the 2 heat 2 cool configuration 26 CNT SVX12C EN...
Страница 56: ...Chapter 6 Sequence of operations for the 4 cool configuration 44 CNT SVX12C EN...
Страница 92: ...Chapter 10 Status indicators for operation and communication 80 CNT SVX12C EN...
Страница 104: ...Chapter 12 Troubleshooting 92 CNT SVX12C EN...
Страница 110: ...Index 98 CNT SVX12C EN...