Diagnosing operational problems
CNT-SVX12C-EN
91
Unit configuration
The controller must be properly configured based on the actual installed end devices and
application. If the unit configuration does not match the actual end device, the outdoor air
damper may not work correctly.
No power to the
controller
If the controller does not have power, the outdoor air damper does not operate. For the
ZN517 controller to operate normally, you must apply an input voltage of 24 Vac. If the
green LED is off continuously, the controller does not have sufficient power or has failed.
Table 33. Outdoor air damper remains open
Probable cause
Explanation
Unit wiring
The wiring between the controller outputs and the outdoor air damper must be present
and correct for normal outdoor air damper operation. Refer to applicable wiring diagram.
Failed end device
Check damper actuator to ensure proper operation.
Normal
operation
The controller opens and closes the outdoor air damper based on the controller’s occu-
pancy mode and fan status. Normally, the outdoor air damper is open during occupied
mode when the fan is running and closed during unoccupied mode.
Manual output test
The controller includes a manual output test sequence you can use to verify output oper-
ation and associated output wiring. However, based on the current step in the test
sequence, the outdoor air damper may be open. Refer to the “Manual output test” on
page 74.
Unit
configuration
The controller must be properly configured based on the actual installed end devices and
application. If the unit configuration does not match the actual end device, the outdoor air
damper may not work correctly.
Table 32. Outdoor air damper remains closed (Continued)
Probable cause
Explanation
Содержание Tracer ZN517
Страница 1: ...CNT SVX12C EN Installation and Operation Tracer ZN517 Unitary Controller...
Страница 2: ......
Страница 3: ...Installation and Operation Tracer ZN517 Unitary Controller CNT SVX12C EN April 2005...
Страница 4: ......
Страница 12: ...Table of contents vi CNT SVX12C EN...
Страница 38: ...Chapter 4 Sequence of operations for the 2 heat 2 cool configuration 26 CNT SVX12C EN...
Страница 56: ...Chapter 6 Sequence of operations for the 4 cool configuration 44 CNT SVX12C EN...
Страница 92: ...Chapter 10 Status indicators for operation and communication 80 CNT SVX12C EN...
Страница 104: ...Chapter 12 Troubleshooting 92 CNT SVX12C EN...
Страница 110: ...Index 98 CNT SVX12C EN...