CNT-SVX12C-EN
81
Chapter 11
General wiring information
This chapter provides specifications and general information about wir-
ing the Tracer ZN517 unitary controller. The controller requires wiring
for:
•
Input/output terminals
•
AC power to the controller
•
Communication-link wiring, if the controller is to communicate with a
building automation system (BAS)
Input/output terminal wiring
All input/output terminal wiring for the Tracer ZN517 unitary controller
is application specific and dependant on the configuration of the control-
ler. For application-specific wiring information and diagrams, see Chapter
3, “Applications for the 2-heat/2-cool configuration”,” Chapter 5, “Applica-
tions for the 4-cool configuration”,” and Chapter 7, “Applications for the
heat pump configuration”.”
Wiring specifications
Input/output terminal wiring must meet the following requirements:
•
All wiring must comply with the National Electrical Code and local
codes.
•
Use only 18 AWG twisted-pair wire with stranded, tinned-copper con-
ductors. (Shielded wire is recommended.)
•
Binary input and output wiring must not exceed 1000 ft (300 m).
•
Analog input wiring must not exceed 300 ft (100 m).
•
Do not run input/output wires in the same wire bundle with any ac
power wires.
Содержание Tracer ZN517
Страница 1: ...CNT SVX12C EN Installation and Operation Tracer ZN517 Unitary Controller...
Страница 2: ......
Страница 3: ...Installation and Operation Tracer ZN517 Unitary Controller CNT SVX12C EN April 2005...
Страница 4: ......
Страница 12: ...Table of contents vi CNT SVX12C EN...
Страница 38: ...Chapter 4 Sequence of operations for the 2 heat 2 cool configuration 26 CNT SVX12C EN...
Страница 56: ...Chapter 6 Sequence of operations for the 4 cool configuration 44 CNT SVX12C EN...
Страница 92: ...Chapter 10 Status indicators for operation and communication 80 CNT SVX12C EN...
Страница 104: ...Chapter 12 Troubleshooting 92 CNT SVX12C EN...
Страница 110: ...Index 98 CNT SVX12C EN...