Chapter 1 Overview and specifications
4
CNT-SVX12C-EN
Storage environment
If you are storing a Tracer ZN517 unitary controller for a substantial
amount of time, store it in an indoor environment that meets the
following requirements:
•
Temperature: From –40° to 185°F (–40° to 85°C)
•
Relative humidity: From 5–95%, noncondensing
Agency listing/compliance
CE—Immunity: EN50082-2:1995
EN61000-6-2:1999
CE—Emissions: EN61000-3-2:1995
EN61000-3-3:1995
EN50081-1:1992 (CISPR 22)
EN55011:1998, Class B
UL and C-UL 916 listed:
Energy management equipment
UL 94-5V (UL flammability rating for plenum use)
FCC Part 15, Class A, CFR 47
Factory default temperature setpoints
The Tracer ZN517 unitary controller relies on a number of temperature
setpoints to control HVAC equipment. Table 1 gives the factory defaults
for these setpoints, which can all be edited with the Rover service tool or a
BAS.
Table 1. Factory default temperature setpoints
Setpoints
Factory defaults
°F (°C)
Default setpoints
Occupied cooling
74.0°F (23.3°C)
Occupied standby cooling
78.0°F (25.6°C)
Unoccupied cooling
85.0°F (29.4°C)
Occupied heating
71.0°F (21.7°C)
Occupied standby heating
67.0°F (19.4°C)
Unoccupied heating
60.0°F (15.6°C)
Occupied setpoint limits
Cooling setpoint high limit
110.0°F (43.3°C)
Cooling setpoint low limit
40.0°F (44.4°C)
Содержание Tracer ZN517
Страница 1: ...CNT SVX12C EN Installation and Operation Tracer ZN517 Unitary Controller...
Страница 2: ......
Страница 3: ...Installation and Operation Tracer ZN517 Unitary Controller CNT SVX12C EN April 2005...
Страница 4: ......
Страница 12: ...Table of contents vi CNT SVX12C EN...
Страница 38: ...Chapter 4 Sequence of operations for the 2 heat 2 cool configuration 26 CNT SVX12C EN...
Страница 56: ...Chapter 6 Sequence of operations for the 4 cool configuration 44 CNT SVX12C EN...
Страница 92: ...Chapter 10 Status indicators for operation and communication 80 CNT SVX12C EN...
Страница 104: ...Chapter 12 Troubleshooting 92 CNT SVX12C EN...
Страница 110: ...Index 98 CNT SVX12C EN...