Chapter 7 Applications for the heat pump configuration
46
CNT-SVX12C-EN
Wiring requirements and options
Table 15 shows required controller inputs for minimal proper operation of
all heat pump applications.
Table 16 shows optional controller inputs and outputs for specific
applications.
Figure 14 on page 47 shows all required and optional components con-
nected for heat pump applications.
Table 15. Required controller inputs for proper operation
Function
Input source
For more information,
see:
24 Vac power
Terminals: GND, 24 V
“AC power wiring” on
page 85
Zone temperature
Terminals: ZN, GND
or communicated
“ZN: Zone tempera-
ture” on page 54
Table 16. Optional controller inputs and outputs for specific
applications
Application
Input/Output
For more information,
see:
Economizing
Input:
DAT (discharge air temperature)
“Economizing” on
page 23
Input:
AI2 (outdoor air temperature)
Outputs:
24 V (24 Vac common)
OPN (binary output)
CLS (binary output)
Discharge air
tempering*
Input: DAT
“Discharge air tem-
pering” on page 24
Demand control
ventilation*
Input:
AI1 (CO
2
sensor)
“Demand control
ventilation” on
page 24
Cascade control
Input: DAT
“Cascade zone con-
trol” on page 20
* In order to use this function, the economizing function must be enabled.
Содержание Tracer ZN517
Страница 1: ...CNT SVX12C EN Installation and Operation Tracer ZN517 Unitary Controller...
Страница 2: ......
Страница 3: ...Installation and Operation Tracer ZN517 Unitary Controller CNT SVX12C EN April 2005...
Страница 4: ......
Страница 12: ...Table of contents vi CNT SVX12C EN...
Страница 38: ...Chapter 4 Sequence of operations for the 2 heat 2 cool configuration 26 CNT SVX12C EN...
Страница 56: ...Chapter 6 Sequence of operations for the 4 cool configuration 44 CNT SVX12C EN...
Страница 92: ...Chapter 10 Status indicators for operation and communication 80 CNT SVX12C EN...
Страница 104: ...Chapter 12 Troubleshooting 92 CNT SVX12C EN...
Страница 110: ...Index 98 CNT SVX12C EN...