Chapter 12 Troubleshooting
88
CNT-SVX12C-EN
Initial troubleshooting
Always perform the initial troubleshooting steps listed in Table 29 before
moving on to the specific area of trouble. Perform the steps in the order
they are listed.
Diagnosing operational problems
After you have performed the initial troubleshooting steps, refer to the
succeeding tables in this chapter to further diagnose the following opera-
tional problems:
•
Fan does not energize (Table 30 on page 89)
•
Heat does not energize (Table 31 on page 90)
•
An outdoor air damper stays closed (Table 32 on page 90)
•
An outdoor air damper stays open (Table 33 on page 91)
Table 29. Initial troubleshooting steps
Step number
Action
Probable cause
Step 1
Look at the red Service LED. If it is flashing once per second, the controller is
not executing the application software because the network connections and
addressing have been removed. For a complete explanation of this LED’s
behavior, see Table 25 on page 76.
Use the Rover service tool or a BAS to restore normal operation. See EMTX-
SVX01B-EN for more information.
Tracer ZN517 is
not configured
Step 2
Look at the green Status LED. It should be on continuously during normal
operation. A blinking Status LED indicates the Tracer ZN517 is performing a
manual output test. For a complete explanation of this LED’s behavior, see
Table 26 on page 77.
Tracer ZN517 is in
manual output test
mode
Step 3
Take your meter (set to measure ac voltage) and measure the voltage across
the ac-power terminals on the Tracer ZN517 (with ac wires connected). See
Figure 32 on page 85.
If you see approximately 24 V (21–27 V) on those terminals, the board is
receiving adequate input power and you likely have a Tracer ZN517 circuit
board problem.
Tracer ZN517 cir-
cuit board prob-
lem
Step 4
Disconnect the ac wires from the input power terminals. Take your meter (set
to measure ac voltage) and measure the voltage across the ac wires. If you
see approximately 0 V, the board is not receiving the power it needs to run.
Input power prob-
lem
Step 5
Reconnect the ac wires to the input power terminals. Perform the manual
output test, which is described in “Manual output test” on page 74.
If the outputs on the controller do not behave as described in the manual
output test (page 74), then you are likely to have a Tracer ZN517 circuit board
problem.
Tracer ZN517 cir-
cuit board prob-
lem
Содержание Tracer ZN517
Страница 1: ...CNT SVX12C EN Installation and Operation Tracer ZN517 Unitary Controller...
Страница 2: ......
Страница 3: ...Installation and Operation Tracer ZN517 Unitary Controller CNT SVX12C EN April 2005...
Страница 4: ......
Страница 12: ...Table of contents vi CNT SVX12C EN...
Страница 38: ...Chapter 4 Sequence of operations for the 2 heat 2 cool configuration 26 CNT SVX12C EN...
Страница 56: ...Chapter 6 Sequence of operations for the 4 cool configuration 44 CNT SVX12C EN...
Страница 92: ...Chapter 10 Status indicators for operation and communication 80 CNT SVX12C EN...
Страница 104: ...Chapter 12 Troubleshooting 92 CNT SVX12C EN...