Chapter 7 Applications for the heat pump configuration
54
CNT-SVX12C-EN
ZN: Zone temperature
The ZN analog input functions as the local (hard-wired) zone temperature
input. The controller receives the temperature as a resistance signal from
a 10 k
Ω
thermistor in a standard Trane zone sensor wired to analog input
ZN. A communicated zone temperature value via the LonTalk communi-
cations link can also be used for controllers operating on a BAS. When
both a hard-wired and communicated zone temperature value is present,
the controller uses the communicated value. If neither a hard-wired nor a
communicated zone temperature value is present, the controller gener-
ates a Space Temperature Failure diagnostic.
The ZN analog input is also used to communicate timed override requests
and cancel requests to the controller for applications utilizing a Trane
zone sensor with the ON and CANCEL button option.
SET: Temperature setpoint
The SET analog input functions as the local (hard-wired) temperature
setpoint input for applications utilizing a Trane zone sensor with a tem-
perature setpoint thumbwheel. Use the Rover service tool or a BAS to
enable or disable the local setpoint input. A communicated setpoint value
via the LonTalk communications link can also be used for controllers
operating on a BAS. If both a hard-wired and a communicated setpoint
value are present, the controller uses the communicated value. If neither
a hard-wired nor a communicated setpoint value is present, the controller
uses the stored default setpoints (configurable using the Rover service
tool or a BAS). If a valid hard-wired or communicated setpoint value is
established and then is no longer present, the controller generates a Local
Space Setpoint Failure diagnostic.
Содержание Tracer ZN517
Страница 1: ...CNT SVX12C EN Installation and Operation Tracer ZN517 Unitary Controller...
Страница 2: ......
Страница 3: ...Installation and Operation Tracer ZN517 Unitary Controller CNT SVX12C EN April 2005...
Страница 4: ......
Страница 12: ...Table of contents vi CNT SVX12C EN...
Страница 38: ...Chapter 4 Sequence of operations for the 2 heat 2 cool configuration 26 CNT SVX12C EN...
Страница 56: ...Chapter 6 Sequence of operations for the 4 cool configuration 44 CNT SVX12C EN...
Страница 92: ...Chapter 10 Status indicators for operation and communication 80 CNT SVX12C EN...
Страница 104: ...Chapter 12 Troubleshooting 92 CNT SVX12C EN...
Страница 110: ...Index 98 CNT SVX12C EN...