Operation
31
BAS-SVX08D-E4
00001
0
1 = stop the circuit 1
bit
00002
1
1 = stop the circuit 2
bit
00003
2
1 = validation of the EVP leaving water setpoint
bit
00004
3
1 = unit runs in heating mode
bit
00005
4
1 = validation of the running mode
bit
00006
5
1 = validation of remote controls
bit
00007
6
1 = low noise is valided
bit
00008
7
1 = validation of the low noise mode
bit
40001
0
EVP water setpoint
Temperature
Bit 7 = validation of remote control
Bit 4 = validation of the running mode
Bit 3 = running mode (0=cool;1=heat)
Bit 2 = validation of the EVP leaving water setpoint
Bit 1 = stop the circuit 2
Bit 0 = stop the circuit 1
bitfield
Bit 3 = validation of EVP water pump control
Bit 2 = EVP water pump command (0=stop;1=start)
Bit 1 = Validation of the low noise mode
Bit 0 = Low noise is validated
bitfield
10001
0
1 = module I/O1 communication fault
bit
10002
1
1 = module I/O2 communication fault
bit
10003
2
1 = module I/O3 communication fault
bit
10004
3
1 = module I/O4 communication fault
bit
10005
4
1 = active remote water setpoint
bit
10006
5
1 = unit in heating mode
bit
10007
6
1 = compressor A1 runs
bit
10008
7
1 = compressor B1 runs
bit
10009
8
1 = liquid valve of circuit 1 open
bit
10010
9
1 = EVP water pump runs
bit
10011
10
1 = EVP resistor is stopped
bit
10012
11
1 = default relay of circuit 1 is ON
bit
10013
12
1 = compressor A2 runs
bit
10014
13
1 = compressor B2 runs
bit
10015
14
1 = liquid valve of circuit 2 opened
bit
10016
15
1 = bypass/reverse cycle of circuit 2 runs
bit
10017
16
1 = default relay of circuit 2 is ON
bit
10018
17
1 = line fan 1 runs
bit
10019
18
1 = Y fan 1 runs
bit
10020
19
1 = delta fan 1 runs
bit)
10021
20
1 = fan 2 runs
bit
10022
21
1 = fans 3 and 4 run
bit
10023
22
1 = warning exits
bit
10024
23
1 = unit or circuit 1 manual reset fault
bit
10025
24
1 = unit or circuit 2 manual reset fault
bit
Table 13 - Data Point List for CGAH/CXAH/CGCL/CCUH/CGWH/RAUL chillers, SMM controller
Data
Type
Binary
Outputs
5/15
Analog
Outputs
6/16
40002
1
40003
2
Binary
Inputs
2
Offset
Point Description
Unit
Function
Modbus
Index
Содержание PIC
Страница 64: ...Maintenance BAS SVX08D E4 64 PIC Status...
Страница 69: ...Maintenance 69 BAS SVX08D E4 Modbus Communication Status...
Страница 78: ...Notes BAS SVX08D E4 78...