Operation
BAS-SVX08D-E4
28
Table 10 - Data Point List for CGAN/CXAN chillers, Tracer CH532 controller Version 1.2
Data Type
Function
Modbus Index
Offset
Point Description
Unit
Binary
Outputs
5/15
00001
0
Chiller Enable/Disable Command (0=Disable)
bit
00002
1
Chiller Mode (0=Cool)
bit
00003
2
Circuit 1 lockout
bit
00004
3
Circuit 2 lockout
bit
Analog
Outputs
6/16
40001
0
Copy of function 5/15 binary points
bitfield
40002
1
Chilled Water Setpoint
Temperature
40003
2
Heating Setpoint
Temperature
Binary Inputs
2
10002
1
Chiller Running Status
bit
10003
2
Circuit 1 Fan 1 output
bit
10004
3
Circuit 1 Fan 2 output
bit
10008
7
Compressor A1 output
bit
10009
8
Compressor B1C1 output
bit
10010
9
Compressor A2 output
bit
10011
10
Compressor B2C2 output
bit
Analog Inputs
4
30001
0
Copy of function 2 binary points
bitfield
30002
1
Active Chilled/Hot Water Setpoint
Temperature
30003
2
Evaporator Leaving Water Temperature
Temperature
30004
3
Evaporator Entering Water Temperature
Temperature
30005
4
Condenser Entering Water Temperature
Temperature
30006
5
Chiller Status (See Appendix)
bitfield