Operation
23
BAS-SVX08D-E4
Table 5 - Data Point List for RTAC chillers (Chiller Profile), Tracer CH530 controller
Data Type
Function
Modbus Index
Offset
Point Description
Unit
Binary
Outputs
5/15
00001
0
Chiller Enable/Disable Command (0=Disable)
bit
00002
1
Chiller Mode (0=Cool)
bit
Analog
Outputs
6/16
40001
0
Copy of function 5/15 binary points
bitfield
40002
1
Chilled Water Setpoint
Temperature
40003
2
Current Limit Setpoint
Percentage
40004
3
Heating Setpoint
Temperature
Binary Inputs
2
10002
1
Chiller Running Status
bit
Analog Inputs
4
30001
0
Copy of function 2 binary points
bitfield
30002
1
Active Chilled/Hot Water Setpoint
Temperature
30003
2
Actual Capacity (Percent Run Load Amps)
Percentage
30004
3
Active Current Limit Setpoint
Percentage
30005
4
Evaporator Leaving Water Temperature
Temperature
30006
5
Evaporator Entering Water Temperature
Temperature
30007
6
Condenser Entering Water Temperature
Temperature
30008
7
Condenser Leaving Water Temperature
Temperature
30009
8
Chiller Status (See Appendix)
bitfield
Содержание PIC
Страница 64: ...Maintenance BAS SVX08D E4 64 PIC Status...
Страница 69: ...Maintenance 69 BAS SVX08D E4 Modbus Communication Status...
Страница 78: ...Notes BAS SVX08D E4 78...
Страница 79: ...Notes 79 BAS SVX08D E4...