Table 7 - Data Point List for RTHD chillers, Tracer CH530 controller
Data Type
Function
Modbus Index
Offset
Point Description
Unit
Binary
Outputs
5/15
00001
0
Chiller Enable/Disable Command (0=Disable)
bit
00002
1
Chiller Mode (0=Cool)
bit
Analog
Outputs
6/16
40001
0
Copy of function 5/15 binary points
bitfield
40002
1
Chilled Water Setpoint
Temperature
40003
2
Current Limit Setpoint
Percentage
40004
3
Heating Setpoint
Temperature
Binary Inputs
2
10002
1
Chiller Running Status
bit
Analog Inputs
4
30001
0
Copy of function 2 binary points
bitfield
30002
1
Active Chilled/Hot Water Setpoint
Temperature
30003
2
Actual Capacity (Percent Run Load Amps)
Percentage
30004
3
Active Current Limit Setpoint
Percentage
30005
4
Evaporator Leaving Water Temperature
Temperature
30006
5
Evaporator Entering Water Temperature
Temperature
30007
6
Condenser Entering Water Temperature
Temperature
30008
7
Condenser Leaving Water Temperature
Temperature
30009
8
Chiller Status (See Appendix)
bitfield
30010
9
Compressor Running Outputs (See Appendix)
bitfield
30011
10
Evaporator Refrigerant Pressure Circuit 1
Pressure
30012
11
Evaporator Refrigerant Temperature Circuit 1
Temperature
30013
12
Condenser Refrigerant Pressure 1
Pressure
30014
13
Condenser Refrigerant Temperature 1
Temperature
30015-30016
14
Starts - Compressor A
None
30017-30018
15
Run Time - Compressor A
Hours
Operation
25
BAS-SVX08D-E4