Table 9 - Data Point List for CGAN/CXAN/CGAM/CXAM/CGC/CCUH/CCUN/CGWH/CGWN/RAUL chillers, Tracer CH530 controller
Data Type
Function
Modbus Index
Offset
Point Description
Unit
Binary
Outputs
5/15
00001
0
Chiller Enable/Disable Command (0=Disable)
bit
00002
1
Chiller Mode (0=Cool)
bit
Analog
Outputs
6/16
40001
0
Copy of function 5/15 binary points
bitfield
40002
1
Chilled Water Setpoint
Temperature
40003
2
Current Limit Setpoint
Percentage
40004
3
Heating Setpoint
Temperature
Binary Inputs
2
10002
1
Chiller Running Status
bit
Analog Inputs
4
30001
0
Copy of function 2 binary points
bitfield
30002
1
Active Chilled/Hot Water Setpoint
Temperature
30003
2
Actual Capacity (Percent Run Load Amps)
Percentage
30004
3
Active Current Limit Setpoint
Percentage
30005
4
Evaporator Leaving Water Temperature
Temperature
30006
5
Evaporator Entering Water Temperature
Temperature
30007
6
Condenser Entering Water Temperature
Temperature
30008
7
Condenser Leaving Water Temperature
Temperature
30009
8
Chiller Status (See Appendix)
bitfield
30010
9
Compressor Running Outputs (See Appendix)
bitfield
30011
10
Condenser Fan Running Outputs (See Appendix)
bitfield
30012
11
Outdoor Air Temperature
Temperature
30013
12
Evaporator Refrigerant Pressure Circuit 1
Pressure
30014
13
Evaporator Refrigerant Pressure Circuit 2
Pressure
30015
14
Evaporator Refrigerant Temperature Circuit 1
Temperature
30016
15
Evaporator Refrigerant Temperature Circuit 2
Temperature
30017
16
Condenser Refrigerant Pressure 1
Pressure
30018
17
Condenser Refrigerant Pressure 2
Pressure
30019
18
Condenser Refrigerant Temperature 1
Temperature
30020
19
Condenser Refrigerant Temperature 2
Temperature
30021-30022
20-21
Starts - Compressor A
None
30023-30024
22-23
Run Time - Compressor A
Hours
30025-30026
24-25
Starts - Compressor B
None
30027-30028
26-27
Run Time - Compressor B
Hours
30029-30030
28-29
Starts - Compressor C
None
30031-30032
30-31
Run Time - Compressor C
Hours
30033-30034
32-33
Starts - Compressor D
None
30035-30036
34-35
Run Time - Compressor D
Hours
30037-30038
36-37
Starts - Compressor E
None
30039-30040
38-39
Run Time - Compressor E
Hours
30041-30042
40-41
Starts - Compressor F
None
30043-30044
42-43
Run Time - Compressor F
Hours