Operation
BAS-SVX08D-E4
22
Trane Equipment Data point List
Table 4 - Data Point List for CVGF / CVHE / CVHF / CVHG chillers, Tracer CH530 controller Version 2.0 and greater
Data Type
Function
Modbus Index
Offset
Point Description
Unit
Binary
Outputs
5/15
00001
0
Chiller Enable/Disable Command
bit
00002
1
Chiller Mode
bit
Analog
Outputs
6/16
40001
0
Copy of function 5/15 binary points
bitfield
40002
1
Chilled Water Setpoint
Temperature
40003
2
Current Limit Setpoint
Percentage
40004
3
Heating Setpoint
Temperature
Binary Inputs
2
10002
1
Chiller Running Status
bit
Analog Inputs
4
30001
0
Copy of function 2 binary points
bitfield
30002
1
Active Chilled/Hot Water Setpoint
Temperature
30003
2
Actual Capacity (Percent Run Load Amps)
Percentage
30004
3
Active Current Limit Setpoint
Percentage
30005
4
Evaporator Leaving Water Temperature
Temperature
30006
5
Evaporator Entering Water Temperature
Temperature
30007
6
Condenser Entering Water Temperature
Temperature
30008
7
Condenser Leaving Water Temperature
Temperature
30009
8
Chiller Status (See Appendix)
bitfield
30010
9
Compressor Running Outputs (See Appendix)
bitfield
30011
10
Evaporator Refrigerant Pressure Circuit 1
Pressure
30012
11
Evaporator Refrigerant Pressure Circuit 2
Pressure
30013
12
Evaporator Refrigerant Temperature Circuit 1
Temperature
30014
13
Evaporator Refrigerant Temperature Circuit 2
Temperature
30015
14
Condenser Refrigerant Pressure 1
Pressure
30016
15
Condenser Refrigerant Pressure 2
Pressure
30017
16
Condenser Refrigerant Temperature 1
Temperature
30018
17
Condenser Refrigerant Temperature 2
Temperature
30019-30020
18-19
Starts - Compressor A
None
30021-30022
20-21
Run Time - Compressor A
Hours
30023-30024
22-23
Starts - Compressor D
None
30025-30026
24-25
Run Time - Compressor D
Hours
Содержание PIC
Страница 64: ...Maintenance BAS SVX08D E4 64 PIC Status...
Страница 69: ...Maintenance 69 BAS SVX08D E4 Modbus Communication Status...
Страница 78: ...Notes BAS SVX08D E4 78...
Страница 79: ...Notes 79 BAS SVX08D E4...