Operation
45
BAS-SVX08D-E4
Data
Type
Offset
Point Description
Function
Modbus
Index
10048
47
Supply Air Tempering is Active (1 = Yes 0 = No)
bit
10049
48
Exhaust Fan is Energized (1 = Yes 0 = No)
bit
10050
49
Condenser Fan A is Energized (1 = Yes 0 = No)
bit
10051
50
Condenser Fan B is Energized (1 = Yes 0 = No)
bit
10052
51
Heat Output 1 is Energized (1 = Yes 0 = No)
bit
10053
52
Heat Output 2 is Energized (1 = Yes 0 = No)
bit
10054
53
Reverse Valve is Energized (1 = Yes 0 = No)
bit
10055
54
Supply Fan is Energized (1 = Yes 0 = No)
bit
10059
58
Clogged Filter Local Input (1 = Yes 0 = No)
bit
10060
59
Compressor 2 Cycling Input (1 = OK 0 = Bad)
bit
10061
60
Compressor 1 Cycling Input (1 = OK 0 = Bad)
bit
10065
64
Default Defrost Flag
bit
10066
65
Demand Defrost Fault C Flag
bit
10067
66
Demand Defrost Fault B Flag
bit
10068
67
Demand Defrost Fault A Flag
bit
10069
68
Fan Failure (1 = Failed 0 = Ok)
bit
10070
69
Heat Failure (1 = Open 0 = Closed)
bit
10071
70
HPC for Compressor 2 (1 = High Press 0 = Normal)
bit
10072
71
HPC for Compressor 1 (1 = High Press 0 = Normal)
bit
30001
0
Outdoor Air Temperature Sensor Value
Temperature
30002
1
Zone Temperature Sensor Value
Temperature
30003
2
Mixed Air Temperature Sensor Value
Temperature
30004
3
Return Air Temperature Sensor Value
Temperature
30005
4
Local Zone Cooling Setpoint Input
Temperature
30006
5
Local Zone Heating Setpoint Input
Temperature
30007
6
Actual Zone Cooling Setpoint
Temperature
30008
7
Actual Zone Heating Setpoint
Temperature
30009
8
Outdoor Air Relative Humidity Sensor Value ( 10.0 to 90.0 %)
Percentage
30010
9
Return Air Relative Humidity Sensor Value ( 10.0 to 90.0 %)
Percentage
30011
10
Local Economizer minimum position Range ( 0.0 to 50.0 %)
Percentage
30012
11
Actual Economizer Damper Position Range ( 0.0 to 100.0 %)
Percentage
30013
12
Number of Cooling Stages Active ( 0 to 3)
None
30014
13
Number of Heating Stages Active ( 0 to 3)
None
30016
15
Reference Enthalpy Switch Settings ( 22, 23, 25 or 27 BTU/LBM)
None
Bit 0 Gas or Electric (1 = Gas Heat 0 = Electric Heat)
Bit 1 Heat Pump (Voyager I & II Only) (1 = Yes 0 = No)
Bit 2 Voyager III Unit (1 = Yes 0 = No)
30018
17
Bit 3 Economizer Installed (1 = Installed 0 = Not Installed)
Bit 4 Gemini Unit (1 = Yes 0 = No)
Bit 5 Not Used - Reserved for UCP
Bit 6 Not Used - Reserved for UCP
Bit 7 Not Used - Reserved for UCP
bitfield
Bit 0 Compressor On or Off (1 = On 0 = Off)
Bit 1 Compressor 1 Locked Out (1 = Yes 0 = No)
Bit 2 HPC for Compressor 1 (1 = High Press 0 = Normal)
30019
18
Bit 3 Compressor 1 Cycling Input (1 = Normal 0 = Disabled)
Bit 4 Compressor 1 Exists (1 = Yes 0 = No)
Bit 5 Compressor 1 is Lead (1 = Yes 0 = No)
Bit 6 Not Used - Reserved for UCP
Bit 7 Not Used - Reserved for UCP
bitfield
Analog
Inputs
4
Binary
Inputs
2
Table 16 - Continued