Operation
BAS-SVX08D-E4
34
Table 14 - Data Point List for RTAA/RTAB/RTXA/RTAD/RTWB/RTRA/RTUB chillers, UCM CLD controller with CSR
Data
Type
Offset
Point Description
Function
Modbus
Index
00001
0
Enable remote setpoints
bit
00002
1
Remote chiller auto/stop (0 = auto, 1 = stop)
bit
00003
2
Enable Hot water setpoint
bit
00004
3
Ice mode (1 = yes, 0 = no)
bit
00005
4
Not used
bit
00006
5
Lock out circuit 1 (1 = yes, 0 = no)
bit
00007
6
Lock out circuit 2 (1 = yes, 0 = no)
bit
00012
11
External hot water setpoint (1 = enable)
bit
00013
12
RTXA unit type (1 = RTXA, 0 = other)
bit
00014
13
RTUA unit type (1 = RTUA, 0 = other)
bit
40001
0
Remote chilled water setpoint
Temperature
40002
1
Remote current limit setpoint
Percentage
40003
2
Copy of function 5/15 binary points
bitfield
40004
3
Front panel hot water setpoint
Temperature
40005
4
Front panel heating design delta temp
Temperature
10001
0
Compressor running bit (1 = any compressor running)
bit
10004
3
Machine manual reset required (1 = active)
bit
10005
4
Machine auto reset (1 = active)
bit
10007
6
Compressor contactor 1 ( 1 = ON, 0 = OFF)
bit
10008
7
Compressor contactor 1 ( 1 = ON, 0 = OFF)
bit
10009
8
Compressor contactor 2 ( 1 = ON, 0 = OFF)
bit
10010
9
Compressor contactor 2 ( 1 = ON, 0 = OFF)
bit
10011
10
Unit heat/cool mode (1 = heat, 0 = cool)
bit
10018
17
Remote setpoints valid (1 = Yes, 0 = No)
bit
10019
18
UCM communication established (1 = Yes, 0 = No)
bit
10020
19
Fan control (1 = enabled, 0 = disabled)
bit
10021
20
SI display units (1 = enabled, 0 = disabled)
bit
10022
21
Under/over voltage detection (1 = enabled, 0 = disabled)
bit
10023
22
Phase unbalance protection (1 = enabled, 0 = disabled)
bit
10024
23
Phase reversal protection (1 = enabled, 0 = disabled)
bit
10025
24
Night noise setback (1 = enabled, 0 = disabled)
bit
10026
25
Reduced intrush starting (1 = enabled, 0 = disabled)
bit
10027
26
Lead/lag (1 = enabled, 0 = disabled)
bit
10028
27
Reset relay 1 ( 1 = ON, 0 = OFF)
bit
10029
28
Condenser fan contactor 4 ( 1 = ON, 0 = OFF)
bit
10030
29
Condenser fan contactor 3 ( 1 = ON, 0 = OFF)
bit
10031
30
Condenser fan contactor 2 ( 1 = ON, 0 = OFF)
bit
10032
31
Condenser fan contactor 1 ( 1 = ON, 0 = OFF)
bit
10033
32
Oil line solenoid valve 1,
female slide valve step load solenoid for 70-125 Ton ( 1 = ON, 0 = OFF)
bit
10034
33
Transition contactor 1 ( 1 = ON, 0 = OFF)
bit
10035
34
Reset relay 1 ( 1 = ON, 0 = OFF)
bit
10036
35
Condenser fan contactor 4 ( 1 = ON, 0 = OFF)
bit
10037
36
Condenser fan contactor 3 ( 1 = ON, 0 = OFF)
bit
10038
37
Condenser fan contactor 2 ( 1 = ON, 0 = OFF)
bit
10039
38
Condenser fan contactor 1 ( 1 = ON, 0 = OFF)
bit
10040
39
Oil line solenoid valve 1,
female slide valve step load solenoid for 70-125 Ton ( 1 = ON, 0 = OFF)
bit
Binary
Outputs
5/15
Analog
Outputs
6/16
Binary
Inputs
2
Unit