Operation
BAS-SVX08D-E4
32
Table 13 - Continued
10026
25
1 = unit or circuit 1 automatic reset fault
bit
10027
26
1 = unit or circuit 2 automatic reset fault
bit
10028
27
1 = circuit 1 is limited or not ready
bit
10029
28
1 = circuit 2 is limited or not ready
bit
10030
29
1 = unit information alarm
bit
10031
30
1 = unit default LED in ON
bit
10032
31
1 = menu B 07 on Remote position
bit
10033
32
1 = unit stopped by external input
bit
10034
33
1 = unit stopped by serial link
bit
10035
34
1 = unit stopped by operator
bit
10036
35
1 = unit stopped by keypad
bit
10037
36
1 = no EVP water flow while the unit is running
bit
10038
37
1 = unit stopped by low ambient
bit
10039
38
1 = no EVP water flow while the unit is stopped
bit
10040
39
1 = EVP water flow established
bit
10041
40
1 = fan speed inverter failure
bit
30001
0
EVP circuit 1 leaving water temperature
Temperature
30002
1
saturated EVP 1 refrigerant temperature
Temperature
30003
2
saturated CDS 1 refrigerant temperature
Temperature
30004
3
EVP circuit 2 leaving water temperature
Temperature
30005
4
saturated EVP 2 refrigerant temperature
Temperature
30006
5
saturated CDS 2 refrigerant temperature
Temperature
30007
6
air temperature
Temperature
30008
7
CDS leaving water temperature
Temperature
30009
8
EVP entering water temperature
Temperature
30010
9
CDS entering water temperature
Temperature
30011
10
saturated EVP 1 refrigerant pressure
Pressure
30012
11
saturated CDS 1 refrigerant pressure
Pressure
30013
12
saturated EVP 2 refrigerant pressure
Pressure
30014
13
saturated CDS 2 refrigerant pressure
Pressure
30015
14
regulation temperature
Temperature
30016
15
active EVP water temperature setpoint
Temperature
30017
16
diagnostic code
None
30018-30019
17-18
start counter of the comrpessor A1
None
30020-30021
19-20
start counter of the compressor A2
None
30022-30023
21-22
start counter of the compressor B1
None
30024-30025
23-24
start counter of the compressor B2
None
30026-30027
25-26
operating hours of the compressor A1
Hours
30028-30029
27-28
operating hours of the compressor A2
Hours
30030-30031
29-30
operating hours of the compressor B1
Hours
30032-30033
31-32
operating hours of the compressor B2
Hours
Bit 7 1 = unit in heating mode
Bit 6 1 = active remote water setpoint
Bit 5 1 = module I/O4 communication fault
Bit 4 1 = module I/O3 communication fault
Bit 3 1 = module I/O2 communication fault
Bit 2 1 = module I/O1 communication fault
bitfield
Analog
Inputs
4
30034
33
Binary
Inputs
2
Data
Type
Offset
Point Description
Unit
Function
Modbus
Index