Installation
9
BAS-SVX08D-E4
Power supply recommendations
Power
requirements
24 VAC/VDC +6V / -12V
50 or 60 Hz
0.5 A maximum
Protection
The PIC device must receive power from a dedicated circuit which is
connected to a dedicated isolation screened transformer. The circuit
must be protected by a 0.5 A / 250V / Medium time lag circuit
breaker/fuse located next to it.
Recommended
wire
The AC/DC-power wiring requires three-wire cable.
The recommended wire is 1.5mm² (16 AWG) copper wire.
Standards
The AC/DC-power wiring complies with IEC or EN 60364-4-41 and
2006/95/EEC for electrical safety.
For compliance with 2006/108/EEC and 89/336/EEC European directive
for electromagnetic compatibility:
- EN 55022 level B
- EN 61000-3-2
- EN 61000-4-2
- EN 61000-4-4
Ground
Connection
The ground connection of the PIC (GND connector) MUST BE
connected to the building earth to prevent electromagnetic
compatibility risks.