64
RT-SVP011A-EN
Troubleshooting
Discharge Air Iso
Damper Failed to
Open
Discharge Air Iso
Damper Failed to
Open
DA Iso Damper
Closed
Unit
Immediate
Shutdown
Latching
All
The Discharge Air Isolation Damper operation was less
than 80% open after 5 minutes.
Remote
Return Air Iso
Damper Failed to
Open
Return Air Iso
Damper Failed to
Open
RA Iso Damper
Closed
Unit
Immediate
Shutdown
Latching
All
The Return Air Isolation Damper operation was less than
80% open after 5 minutes.
Remote
Discharge Air Iso
Damper Failed to
Close
Discharge Air Iso
Damper Failed to
Close
DA Iso Damper
Open
Unit
Warning
Non-Latching All
The Discharge Air Isolation is more than 20% opened
when it should be closed after 5 minutes.
Remote
Return Air Iso
Damper Failed to
Close
Return Air Iso
Damper Failed to
Close
RA Iso Damper
Open
Unit
Warning
Non-Latching All
The Return Air Isolation Damper is more than 20%
opened when it should be closed after 5 minutes.
Remote
Discharge Air Iso
Damper Closed
Discharge Air Iso
Damper Closed
DA Iso Damper
Closed
Unit
Immediate
Shutdown
Latching
All
The Discharge Air Isolation Damper was less than 80%
open any time the unit is running.
Remote
Return Air Iso
Damper Closed
Return Air Iso
Damper Closed
RA Iso Damper
Closed
Unit
Immediate
Shutdown
Latching
All
The Return Air Isolation Damper was less than 80% open
any time the unit is running.
Remote
Discharge Air Iso
Damper Input
Discharge Air Iso
Damper Input
DA Iso Damper
Input
Unit
Immediate
Shutdown
Latching
All
The Discharge Air Isolation Damper Voltage Input has
failed out of range. This voltage is an indication of actual
damper position.
Remote
Return Air Iso
Damper Input
Return Air Iso
Damper Input
RA Iso Damper
Input
Unit
Immediate
Shutdown
Latching
All
The Return Air Isolation Damper Voltage Input has failed
out of range. This voltage is an indication of actual
damper position.
Remote
Diagnostic Name
and Source
Affects
Target
Severity
Persistence
Active
Modes
[Inactive