8
RT-SVP011A-EN
Introduction
Specifications and Agency Compliance
Controller and Service Tool Requirements
Tracer TU
Tracer TU Service Tool Version 10.2 or higher is only required for TGP2 and modifications done in
the field.
Note:
Tracer TU is not needed for normal operation. If you need to perform configuration changes,
add new features, or customize the operation of the equipment, contact your local Trane
office.
Web UI
To perform firmware updates, setup communication protocols, backup and restore, scheduling,
and create users or custom trend views connect using Web UI:
1. Connect a laptop to the USB service tool port using a USB 2.0 A to Be cable.
2. Open a web browser and connect to http://198.80.81.1 to access Web UI.
Figure 1. Web UI connection
Specification
Input power:
24 Vac +/- 15%, 21 VA, 50 or 60 Hz
Storage temperature:
-67°F to 203°F (-55°C to 95°C)
Humidity: Between 5% and 100% (non-condensing)
Operating temperature:
Temperature: -40°F to 158°F (-40°C to 70°C)
Humidity: Between 5% and 100% (non-condensing)
Mounting weight:
Mounting surface must support 1.625 lb (0.737 kg)
Mounting Type: VESA (75 mm x 75 mm)
Environmental rating (enclosure):
IP56 (dust and strong water protected) with use of an optional Sealed Ethernet Cable
Agency Compliance
• UL916 PAZX, Open Energy Management Equipment
• UL94-5V, Flammability
• FCC CFR Title 47, Part 15.109: Class A Limit, (30 MHz—4 GHz)
• CE EMC Directive 2004/108/EC
• CE EMC Directive 2004/108/EC
Содержание IntelliPak
Страница 16: ...16 RT SVP011A EN Alarms Figure 7 Web UI Alarm Configuration screen...
Страница 85: ...RT SVP011A EN 85 Notes Notes...
Страница 86: ...86 RT SVP011A EN Notes...
Страница 87: ...RT SVP011A EN 87 Notes...