Troubleshooting
VFD Fault
Condenser Fan -
Cktx
VFD Fault
Condenser Fan -
Cktx
VFD Fault
Condenser Fan
Circuit
Warning
with
Special Action
Latching
All
VFD Fault. Numerous drive faults can cause this general
fault. Reference the TR170 Installation and Operating
manual for a list of fault codes and descriptions.
Condenser fan control will revert to fixed-speed fan
algorithm using remaining fans.
The Latching behavior for this diagnostic is latched in the
drive. When the drive diagnostics are reset this
diagnostic will be cleared in the Symbio 800 controller.
Local
VFD Condenser
Fan Motor
Current Overload
– Cktx
VFD Condenser
Fan Motor
Current Overload
- Cktx
VFD Cond Fan
Current Ovld
Circuit
Warning
with
Special Action
Latching
All
The inverter peak current of approximately 200% of rated
current was exceeded for 1.5 seconds. Condenser fan
control will revert to fixed-speed fan algorithm using
remaining fans.
The Latching behavior for this diagnostic is latched in the
drive. When the drive diagnostics are reset this diagnostic
will be cleared in the Symbio 800 controller.
This drive alarm may be Trip Locked at the TR170 drive.
If the drive determines that the condition could cause
damage to the drive, the drive protects itself by
generating a Trip Lock that can only be cleared by cycling
power.
Local
VFD Condenser Fan
Ground Fault -
Cktx
VFD Condenser Fan
Ground Fault -
Cktx
VFD Cond Fan
Ground Fault
Circuit
Warning
with
Special Action
Latching
All
An earth ground fault has resulted in a discharge from the
output phases to ground, either in the cable between the
adjustable frequency drive and the motor or in the motor
itself. Condenser fan control will revert to fixed-speed fan
algorithm using remaining fans.
Further operation of the
failed fan is not recommended until measurements to
ground can be taken from the motor leads and the ground
fault removed.
The Latching behavior for this diagnostic is latched in the
drive. When the drive diagnostics are reset this
diagnostic will be cleared in the Symbio 800 controller.
This drive alarm may be Trip Locked at the TR170 drive.
If the drive determines that the condition could cause
damage to the drive, the drive protects itself by
generating a Trip Lock that can only be cleared by cycling
power.
Local
VFD Condenser Fan
Short Circuit -
Cktx
VFD Condenser Fan
Short Circuit -
Cktx
VFD Cond Fan
Short Circuit
Circuit
Warning
with
Special Action
Latching
All
A short circuit in the motor windings or the motor
terminals was
detected. Condenser fan control will revert to fixed-speed fan
algorithm using remaining fans
.
Further operation of the failed fan
is not recommended until the short circuit is removed.
The Latching behavior for this diagnostic is latched in the
drive. When the drive diagnostics are reset this
diagnostic will be cleared in the Symbio 800 controller.
This drive alarm may be Trip Locked at the TR170 drive.
If the drive determines that the condition could cause
damage to the drive, the drive protects itself by
generating a Trip Lock that can only be cleared by cycling
power.
Local
Diagnostic Name
and Source
Affects
Target
Severity
Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level