Troubleshooting
Supply Air High
Static Pressure
Lockout
Supply Air High
Static Pressure
Lockout
SA High Static
Press Lock
Unit
Immediate
Shutdown
with Special
Action
Latching
All
The supply air pressure has exceeded the Supply Air
Pressure High Limit Setpoint the 3
rd
consecutive time
while the unit is operating in any mode.
VOM Behavior: During VOM this diagnostic is not
generated. See Supply Fan Control specification for more
information.
Remote
Discharge Air
High
Temperature
Detected
Discharge Air
High
Temperature
Detected
Discharge Air
High Temp
Unit
Immediate
Shutdown
Latching
All
If the Discharge air temperature exceeds 200F then an
Immediate Stop will be generated. This is intended to
shut the unit down the unit if high duct temperatures
exist.
This must be from a Local Discharge Air Temperature
sensor (not an arbitrated value)
Local
Return Air High
Temperature
Detected
Return Air High
Temperature
Detected
Return Air High
Temp
Unit
Immediate
Shutdown
Latching
All
If the Return air temperature exceeds 135F then an
Immediate Stop will be generated. This is intended to
shut the unit down the unit if high duct temperatures
exist.
This Diagnostic is only available if Comparative Enthalpy
is Installed in configuration and the Return Air
Temperature is operating normally.
Local
Ventilation
Override Mode A
Ventilation
Override Mode A
Ventilation
Override Mode A
Unit
Warning
Non-Latching All
The unit is following VOM mode A.
This diagnostic is generated to notify BAS integrators as
to the presence of VOM mode.
Local
Ventilation
Override Mode B
Ventilation
Override Mode B
Ventilation
Override Mode B
Unit
Warning
Non-Latching All
The unit is following VOM mode B.
This diagnostic is generated to notify BAS integrators as
to the presence of VOM mode.
Local
Ventilation
Override Mode C
Ventilation
Override Mode C
Ventilation
Override Mode C
Unit
Warning
Non-Latching All
The unit is following VOM mode C.
This diagnostic is generated to notify BAS integrators as
to the presence of VOM mode.
Local
Ventilation
Override Mode D
Ventilation
Override Mode D
Ventilation
Override Mode D
Unit
Warning
Non-Latching All
The unit is following VOM mode D.
This diagnostic is generated to notify BAS integrators as
to the presence of VOM mode.
Local
Ventilation
Override Mode E
Ventilation
Override Mode E
Ventilation
Override Mode E
Unit
Warning
Non-Latching All
The unit is following VOM mode E.
This diagnostic is generated to notify BAS integrators as
to the presence of VOM mode.
Local
Diagnostic Name
and Source
Affects
Target
Severity
Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level