66
RT-SVP011A-EN
Troubleshooting
Suction
Temperature 2
Cktx
Suction
Temperature 2
Cktx
Suction Temp
Sensor
Circuit
Immediate
Shutdown
Latching
All
The suction temperature sensor has failed out of range. Remote
Suction Pressure
Sensor Cktx
Suction Pressure
Sensor Cktx
Suction Press
Sensor
Circuit
Immediate
Shutdown
Latching
All
The suction pressure sensor has failed out of range.
Remote
Discharge
Pressure Sensor
Cktx
Discharge
Pressure Sensor
Cktx
Discharge Press
Sensor
Circuit
Immediate
Shutdown
Latching
All
The discharge pressure sensor has failed out of range. Remote
Mixed Air
Temperature
Sensor Evapy
Mixed Air
Temperature
Sensor Evapy
Mixed Air Temp
Sensor
DX
Cooling
Normal
Shutdown
Latching
All
Temperature sensor has failed out of range.
Remote
Evap Leaving Air
Coil Temp X
Sensor
Evap Leaving Air
Coil Temp X
Sensor
Evap Lvg Air
Temp Sensor
Unit
Warning with
Special Action
Latching
All
Temperature sensor has failed out of range.
The DX cooling continues to run but reheat for
dehumidification is stopped.
Remote
Outdoor Air
Temperature
Sensor
Outdoor Air
Temperature
Sensor
Outdoor Air
Temp Sensor
DX
Cooling
Warning
Non-Latching All
Temperature sensor has failed out of range.
Remote
MP: Invalid
Configuration
MP: Invalid
Configuration
MP: Invalid
Configuration
N/A
N/A
Latching
All
MP has an invalid configuration based on the current
software installed.
Remote
Diagnostic Name
and Source
Affects
Target
Severity
Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level