RT-SVP011A-EN
69
Troubleshooting
Hydronic Heat
Actuator Failed
Open
Hydronic Heat
Actuator Failed
Open
HH Actuator Fail
Closed
Unit
Warning
Non- Latching All
The hydronic heat actuator position has been greater
than the actuator command by 10% for 5 continuous
minutes.
Remote
Chilled Water
Actuator Failed
Closed
Chilled Water
Actuator Failed
Closed
CW Actuator Fail
Closed
Unit
Warning
Non- Latching All
The chilled water actuator position has been lower than
the actuator command by 10% for 5 continuous minutes.
Remote
Chilled Water
Actuator Failed
Open
Chilled Water
Actuator Failed
Open
CW Actuator Fail
Closed
Unit
Warning
Non- Latching All
The chilled water actuator position has been greater than
the actuator command by 10% for 5 continuous minutes.
Remote
Outdoor Air
Damper Input
Outdoor Air
Damper Input
OA Damper Input
Unit
Warning
Non- Latching All
The Outdoor Air Damper Input has failed out of range.
This voltage is an indication of actual damper position.
Remote
Relief Air Damper
Input
Relief Air Damper
Input
Rel Air Damper
Input
Unit
Warning
Non- Latching All
The Relief Air Damper Input has failed out of range. This
voltage is an indication of actual damper position.
Remote
Return Air
Humidity Sensor
Return Air
Humidity Sensor
RA Humidity
Sensor
Unit
Warning
with
Special
Action
Non-Latching All
The Return Air Humidity sensor has failed out of range.
This drives a ‘fall back’ response to Enthalpy Economizer
and Energy Wheel decisions.
Remote
Return Air
Temperature
Sensor
Return Air
Temperature
Sensor
RA Temperature
Sensor
Unit
Warning
with
Special
Action
Non-Latching All
The Return Air Temperature sensor has failed out of
range.
This drives a ‘fall back’ response to Enthalpy Economizer,
Energy Wheel, and possibly Rapid Restart decisions.
Remote
Outdoor Air
Humidity Sensor
Outdoor Air
Humidity Sensor
OA Humidity
Sensor
Unit
Warning
Non-Latching All
The Outdoor Air Humidity sensor has failed out of range.
No action is taken for this sensor failure only the Outdoor
Air Humidity Sensor Active has special action.
Remote
Diagnostic Name
and Source
Affects
Target
Severity
Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level
Содержание IntelliPak
Страница 16: ...16 RT SVP011A EN Alarms Figure 7 Web UI Alarm Configuration screen...
Страница 85: ...RT SVP011A EN 85 Notes Notes...
Страница 86: ...86 RT SVP011A EN Notes...
Страница 87: ...RT SVP011A EN 87 Notes...