68
RT-SVP011A-EN
Troubleshooting
Relief Air Damper
Failed Closed
Relief Air Damper
Failed Closed
Rlf ir Damper Fail
Closed
Unit
Warning
Non- Latching All
The relief air damper position has been lower than the
damper command by 10% for 5 continuous minutes.
Remote
Relief Air Damper
Failed Open
Relief Air Damper
Failed Open
Rlf Air Damper
Fail Open
Unit
Warning
Non- Latching All
The relief air damper position has been greater than the
damper command by 10% for 5 continuous minutes.
Remote
OA Bypass
Damper Failed
Closed
OA Bypass
Damper Failed
Closed
OA Bypass Dmp
Fail Closed
Unit
Warning
Non- Latching All
The outdoor air bypass damper position has been lower
than the damper command by 10% for 5 continuous
minutes.
Remote
OA Bypass
Damper Failed
Open
OA Bypass
Damper Failed
Open
OA Bypass Dmp
Fail Open
Unit
Warning
Non- Latching All
The outdoor air bypass damper position has been greater
than the damper command by 10% for 5 continuous
minutes.
Remote
RA Bypass
Damper Failed
Closed
RA Bypass
Damper Failed
Closed
RA Bypass Dmp
Fail Closed
Unit
Warning
Non- Latching All
The return air bypass damper position has been lower
than the damper command by 10% for 5 continuous
minutes.
Remote
RA Bypass
Damper Failed
Open
RA Bypass
Damper Failed
Open
RA Bypass Dmp
Fail Open
Unit
Warning
Non- Latching All
The return air bypass damper position has been greater
than the damper command by 10% for 5 continuous
minutes.
Remote
Hydronic Heat
Actuator Failed
Closed
Hydronic Heat
Actuator Failed
Closed
HH Actuator Fail
Closed
Unit
Warning
Non- Latching All
The hydronic heat actuator position has been lower than
the actuator command by 10% for 5 continuous minutes.
Remote
Diagnostic Name
and Source
Affects
Target
Severity
Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level