RT-SVP011A-EN
67
Troubleshooting
Starts/Hours
Modified -
Cprsrxy
Starts/Hours
Modified -
Cprsrxy
Starts/Hours
Modified - Cprsrxy
Cprsr
Warning
Non-Latching All
The current value for the cumulative compressor starts
and or hours for the given compressor have been
modified by a write override from TU.
Remote
High Compressor
Press Differential
Cktx
High Compressor
Press Differential
Ckt1
High Cprsr Press
Diff x
Circuit
Immediate
Shutdown
Non -Latching Ckt
Energized
Compressor involute pressure differential exceeded
allowable limits.
Remote
High Compressor
Press Diff Lockout
Cktx
High Compressor
Press Diff Lockout
Cktx
High Cprsr Press
Diff Lock x
Circuit
Immediate
Shutdown
Latching
Ckt
Energized
Compressor involute pressure differential exceeded
allowable limits.
Remote
Unit Not
Economizing
When It Should
Unit Not
Economizing
When It Should
Unit Not Econ
When It Should
Unit
Warning
Non- Latching Cooling w/
Economizer
Enabled
The unit is in active economizer cooling. The economizer
(OAD) command has been greater than the economizer
position by 10% for 5 continuous minutes.
Remote
Unit Economizing
When It Should
Not
Unit Economizing
When It Should
Not
Unit Econ When It
Should Not
Unit
Warning
Non- Latching Cooling w/
Economizer
Enabled
The unit is in active economizer cooling. The economizer
(OAD) command has been lower than the economizer
position by 10% for 5 continuous minutes.
Remote
Outdoor Air
Damper Not
Modulating
Outdoor Air
Damper Not
Modulating
OA Damper Not
Modulating
Unit
Warning
Non- Latching All w/o
‘Cooling w/
Economizer
Enabled’
The unit is in any mode that is not active economizer
cooling. The OAD position has been lower than the
minimum ventilation command by 10% for 5 continuous
minutes.
Remote
Excessive
Outdoor Air
Excessive
Outdoor Air
Excessive
Outdoor Air
Unit
Warning
Non- Latching All w/o
‘Cooling w/
Economizer
Enabled’
The unit is in any mode that is not active economizer
cooling. The OAD position has been greater than the
minimum ventilation command by 10% for 5 continuous
minutes.
Remote
Diagnostic Name
and Source
Affects
Target
Severity
Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level