Troubleshooting
Troubleshooting
This section describes the possible error messages and other issues that you may encounter while
using the Tracer TD7 display.
Identifying and Diagnosing Issues
Diagnostic Name
and Source
Affects
Target
Severity
Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level
VFD Fault Supply
Fan - 1
VFD Fault Supply
Fan - 1
VFD Fault Supply
Fan - 1
Unit
Warning with
Special Action
Latching
All
VFD Fault. Numerous drive faults can cause this general
fault. Reference the TR150 Installation and Operating
manual for a list of fault codes and descriptions.
Failure with Supply Fan 2 available:
Generate Supply Fan 1 Proving Failure
Diagnostic and Lockout all heating operation.
Failure with Supply Fan 2 NOT available:
Generate Supply Fan 1 Proving Failure
and Shutdown the unit
The Latching behavior for this diagnostic is latched in the
drive. When the drive diagnostics are reset this diagnostic
will be cleared in the Symbio 800 controller.
Local
VFD Fault Supply
Fan - 2
VFD Fault Supply
Fan - 2
VFD Fault Supply
Fan - 2
Unit
Warning with
Special Action
Latching
All
VFD Fault. Numerous drive faults can cause this general
fault. Reference the TR150 Installation and Operating
manual for a list of fault codes and descriptions.
Failure with Supply Fan 1 available:
Generate Supply Fan 2 Proving Failure
Diagnostic and Lockout all heating operation.
Failure with Supply Fan 1 NOT available:
Generate Supply Fan 2 Proving Failure
And Shutdown the unit
The Latching behavior for this diagnostic is latched in the
drive. When the drive diagnostics are reset this diagnostic
will be cleared in the Symbio 800 controller.