50
CAUJ-SVX01E-EN
Table 19.
Recommended refrigerant capacities
Unit Size
Operating Charge per Circuit
(a)
Condenser Storage Capacity
(b)
C20
12
19
C25
12
19
C30
12
19
C40
11
24
C50
12
25
C60
13
32
C80
29
47
D10
30
50
D12
33
63
(a)
CAUJ-C20 through C30 are single circuit units. CAUJ C40 through D12 are dual circuit units.
(b)
Pounds R-410A per circuit at 95°F ambient, 95% full.
Table 20.
Liquid line & drier refrigerant requirements
Liquid Line O.D.
Liquid Line Charge
Sporlan Part No
Drier Refrigerant Charge
5/8"
1.827
C-305-S
1 lb. - 1 oz.
3/4"
2.728
C-307-S
1 lb. - 1 oz.
C-417-S
1 lb. - 8 oz.
7/8"
3.790
C-307-S
1 lb. - 1 oz.
C-417-S
1 lb. - 8 oz.
1-1/8"
6.461
C-419-S
1 lb. - 8 oz.
Note:
Refrigerant charge given in ounces per foot.
Table 21.
Minimum starting ambient temperatures
Standard Units
Low Ambient Units
Unit Size (tons)
With HGBP
No HGBP
With HGBP
No HGBP
20-60
40
30
10
0
80-120
40
10
0
Note:
Minimum starting ambients in degrees F, based on unit at minimum step of unloading and 5 mph wind across condenser.
S
Stta
arrtt--U
Up
p