38
CAUJ-SVX01E-EN
Installation Electrical
Electrical
N
No
otte
e:: Local codes may take precedence.
Table 13.
CAUJ electrical data
Unit Size
(ton)
Rated
Voltage
(a)
Unit Characteristics
Condenser Fan Motor
(b)
MCA
(c)
Max Fuse
(d)
kW
(e)
Qty
FLA
HP
LRA
20
200-230/60/3
9.2
15
0.9
2
4.1
1
20.7
460/60/3
4.1
15
0.9
2
1.8
1
9.0
575/60/3
3.2
15
0.9
2
1.4
1
7.2
25
200-230/60/3
13.3
20
0.9
3
4.1
1
20.7
460/60/3
5.9
15
0.9
3
1.8
1
9.0
575/60/3
4.6
15
0.9
3
1.4
1
7.2
30
200-230/60/3
13.3
20
0.9
3
4.1
1
20.7
460/60/3
5.9
15
0.9
3
1.8
1
9.0
575/60/3
4.6
15
0.9
3
1.4
1
7.2
40
200-230/60/3
17.4
20
0.9
4
4.1
1
20.7
460/60/3
7.7
15
0.9
4
1.8
1
9.0
575/60/3
6.0
15
0.9
4
1.4
1
7.2
50
200-230/60/3
25.6
30
0.9
6
4.1
1
20.7
460/60/3
11.3
15
0.9
6
1.8
1
9.0
575/60/3
8.8
15
0.9
6
1.4
1
7.2
60
200-230/60/3
25.6
30
0.9
6
4.1
1
20.7
460/60/3
11.3
15
0.9
6
1.8
1
9.0
575/60/3
8.8
15
0.9
6
1.4
1
7.2
80
200/60/3
34
40
0.9
8
4.1
1
20.7
230/60/3
34
40
0.9
8
4.1
1
20.7
460/60/3
15
20
0.9
8
1.8
1
9
575/60/3
12
15
0.9
8
1.4
1
7.2
100
200/60/3
50
60
0.9
12
4.1
1
20.7
230/60/3
50
60
0.9
12
4.1
1
20.7
460/60/3
22
25
0.9
12
1.8
1
9
575/60/3
17
20
0.9
12
1.4
1
7.2
120
200/60/3
50
60
0.9
12
4.1
1
20.7
230/60/3
50
60
0.9
12
4.1
1
20.7
460/60/3
22
25
0.9
12
1.8
1
9
575/60/3
17
20
0.9
12
1.4
1
7.2
(a)
Voltage Utilization Range is +/- 10% of Rated voltage (use range): 200/60/3 (180-220), 230/60/3 (208-254), 460/60/3 (414-506), 575/60/3 (516-633)
(b)
Electrical information is for each individual motor.
(c)
Minimum circuit ampacity (MCA) is 125 percent of the RLA of one compressor motor plus the total RLA of the remaining motors.
(d)
Maximum fuse size is permitted by NEC 440-22 is 300 percent of one motor RLA plus the RLA of the remaining motors
(e)
All kW values taken at conditions of 45°F saturated suction temperature at the compressor and 95°F ambient.