42
CAUJ-SVX01E-EN
Operating Principles
Component Locations
Condenser Fans
Figure 24.
Condenser fan locations: 20 to 60 ton units
50 & 60 T o n
Control P anel
Low Ambient
Dampers
2B4
2B5
2B6
2B1
2B3
2B2
40 T o n
Control P anel
Low Ambient
Dampers
2B4
2B5
2B1
2B2
20 T o n
25 & 30 T o n
Control P anel
Low Ambient
Damper
2B1
2B3
2B2
Control P anel
Low Ambient
Damper
2B1
2B2
Figure 25.
Condenser fan locations: 80 to 120 ton units
80 T o n
100 & 120 T
o n
Control P anel
Low Ambient
Dampers
Control P anel
Low Ambient
Dampers
4B4
4B5
5B5
5B4
4B1
5B2
5B1
4B4
4B5
4B6
5B5
4B1
4B2
4B3
5B2
5B4
5B6
5B1
5B3
4B2
Unit Operation
Standard air cooled condensers function as the
outdoor condensing units for appropriately sized split
refrigeration systems. These units, operating in
conjunction with a matched indoor compressor/
evaporator configuration, provide refrigerant
condensing for these systems down to a normal
ambient temperature of 40º F. Operation to 0º F ambient
is possible with the addition of externally mounted low
ambient dampers.
All condenser fans are direct drive, 26 inch propeller
type. They are driven by 1 HP thermally protected
motors.
When wired properly, the unit will start and operate
satisfactorily as long as the operating temperature is