48
CAUJ-SVX01E-EN
Start-Up
Verifying Proper Condenser Fan
Rotation
W
WA
AR
RN
NIIN
NG
G
R
Ro
otta
attiin
ng
g C
Co
om
mp
po
on
ne
en
ntts
s!!
F
Fa
aiillu
urre
e tto
o d
diissc
co
on
nn
ne
ecctt p
po
ow
we
err b
be
effo
orre
e s
se
errv
viic
ciin
ng
g cco
ou
ulld
d
rre
es
su
ulltt iin
n rro
otta
attiin
ng
g cco
om
mp
po
on
ne
en
nttss ccu
uttttiin
ng
g a
an
nd
d s
slla
as
sh
hiin
ng
g
tte
ec
ch
hn
niicciia
an
n w
wh
hiicch
h cco
ou
ulld
d rre
essu
ulltt iin
n d
de
ea
atth
h o
orr sse
erriio
ou
uss
iin
njju
urry
y..
D
Diisscco
on
nn
ne
ec
ctt a
allll e
elle
eccttrriicc p
po
ow
we
err,, iin
nccllu
ud
diin
ng
g rre
em
mo
otte
e
d
diis
scco
on
nn
ne
eccttss b
be
effo
orre
e s
se
errv
viic
ciin
ng
g.. F
Fo
ollllo
ow
w p
prro
op
pe
err
llo
oc
ckko
ou
utt//tta
ag
go
ou
utt p
prro
occe
ed
du
urre
es
s tto
o e
en
nssu
urre
e tth
he
e p
po
ow
we
err
c
ca
an
n n
no
ott b
be
e iin
na
ad
dv
ve
errtte
en
nttlly
y e
en
ne
errg
giizze
ed
d..
1.
“Open” the field supplied disconnect switch or
circuit protector switch that provides power to the
compressor unit and lock it in the “Off” position.
2. Open the disconnect switch or circuit protector
switch that provides power to the condensing unit.
3. To install temporary jumpers:
a. For 20-60 ton units: install temporary jumpers
across terminals 1TB2-1 to 1TB2-3, 1TB2-1 to
1TB2-8, and the applicable cycling controls, i.e.,
pressure switches and ambient thermostats, to
start the condenser fans, as illustrated in
component location drawings.
b. For 80-120 ton units: Install temporary jumpers
across terminals 1TB4-7 to 1TB4-9, 1TB4-7 to
1TB4-11, and the applicable cycling controls, i.e.,
pressure switches and ambient thermostats, to
start the condenser fans, as illustrated in
component location drawings.
4. “Close” the disconnect switch or circuit protector
switch that provides power to the condensing unit.
Turn the control circuit switch 1S5 to the “On”
position. The fans will start when the power is
applied.
5. Check the condenser fans for proper rotation. The
direction of rotation is clockwise when viewed from
the top of the unit.
6. Turn the field supplied disconnect switch or circuit
protector switch that provides power to the
condensing unit to the “Off” position. Lock the
disconnect switch in the open position while
working at the unit.
7.
Interchange any two of the field connected main
power wires at the unit terminal block 1TB1 in the
unit control panel.
8. Remove all temporary jumpers previously installed
in step 3 of “Verifying Proper Condenser Fan
Rotation”.
N
No
otte
e:: Interchanging “Load” side power wires at the
fan contactors will only affect the individual
fan rotation. Ensure that the voltage phase
sequence at the main terminal block 1TB1 is
ABC as outlined in the “Electrical Phasing”
section.
9. “Open” the field supplied disconnect switch
upstream of the unit. Lock the disconnect switch in
the “Open” position while working at the unit.
10. Interchange any two of the fan motor leads at the
fan contactor for each fan that is rotating
backwards.
11. Remove all temporary jumpers previously installed
in step 3 of “Verifying Proper Condenser Fan
Rotation”.
All Fans are Rotating Backwards
1.
Turn the field supplied disconnect switch or circuit
protector switch that provides power to the
condensing unit to the “Off” position. Lock the
disconnect switch in the open position while
working at the unit.
2. Interchange any two of the field connected main
power wires at the unit terminal block 1TB1 in the
unit control panel.
3. Remove all temporary jumpers previously installed
in step 3 of Verifying Proper Condenser Fan
Rotation section.
N
No
otte
e:: Interchanging “Load” side power wires at the fan
contactors will only affect the individual fan
rotation. Ensure that the voltage phase sequence
at the main terminal block 1TB1 is ABC as
outlined in the “Electrical Phasing” section.
Some Fans are Rotating Backwards
1.
“Open” the field supplied disconnect switch
upstream of the unit. Lock the disconnect switch in
the “Open” position while working at the unit.
2. Interchange any two of the fan motor leads at the
fan contactor for each fan that is rotating
backwards.
3. Remove all temporary jumpers previously installed
in step 3 of Verifying Proper Condenser Fan
Rotation section.
Low Ambient Damper
Adjustment
(Factory or Field Installed)
When a unit is ordered with the low ambient option
(model number digit 11 =1), a damper is factory
installed over the lead condenser fan for each