8
CAUJ-SVX01E-EN
General Data
Table 1.
General data — CAUJ condensers
Unit Size (tons)
20
25
30
40
50
60
80
100
120
Condenser Fan Data
Type/Drive Type
Prop/Direct
Qty
2
3
3
4
6
6
8
12
12
Diameter
in
26
26
26
26
26
26
26
26
26
Power/motor
hp
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
Nominal Total Airflow
cfm
14600
20700
20700
26790
36890
40490
56490
73890
76280
Condenser Coil Data
Type
Microchannel
Number of Coils
2
2
2
2
2
2
4
4
4
Size
in
42x71
42x71
42x71
59x71
51x96
51x96
59x71
51x96
64x96
Face Area
ft
2
41.4
41.4
41.4
58.2
68.0
68.0
116.4
136.0
170.7
Rows/Fin Per Ft.
1/240
1/240
1/240
1/240
1/240
1/240
1/240
1/240
1/240
Storage Capacity
(a)
lbs
18.7
18.7
18.7
23.5
25.0
25.0
47.1
50.0
62.9
Refrigerant Data
(b)
Type
R-410A
Operating Charge
(c)
lbs
11.9
11.8
11.8
22.7
23.4
23.8
57.1
59.1
65.3
Outdoor Air Temperature for Mechanical Cooling
Standard Ambient
Operating Range
°F
40-125
40-125
40-125
40-125
40-125
40-125
40-125
40-125
40-125
Low Ambient Option
°F
0-125
0-125
0-125
0-125
0-125
0-125
0-125
0-125
0-125
(a)
Condenser storage capacity is given at conditions of 95°F outdoor temperature, and 95% full.
(b)
Condensing units are shipped with nitrogen holding charge only.
(c)
Operating charge is approximate for condensing unit only, and does not include charge for low side or interconnecting lines. Condensing units are shipped
with a nitrogen holding charge only.