22
WX9 ASD Installation and Operation Manual
Terminal Descriptions
Note:
The programmable terminal assignments may be accessed and changed from the
default settings as mapped on
or via the
Direct Access
method: Program
Direct Access
applicable parameter number
. See the section titled
for the applicable
Direct Access
parameter numbers. For
additional information on terminal assignments and default setting changes, see the
section titled
Default Setting Changes on pg. 39
,
, and
Note:
Cable/Terminal Specifications on pg. 203
for the ASD conductor
and terminal electrical specifications.
ST
— The default terminal assignment is
Standby
mode controller. As the default setting, this terminal
must be activated for normal system operation (system is in
Standby
when activated). The
ST
terminal
is activated by connecting
CC
to this terminal (Sink mode). If not connected to
CC
,
Off
is displayed on
the LCD screen. This input terminal may be programmed to any of the functions that are listed in
).
RES
— The default terminal assignment is
Reset
. As the default setting, this terminal resets any active
alarms or faults. The
RES
terminal is activated by connecting
CC
to this terminal (Sink mode). A
momentary connection to
CC
resets the ASD and any fault indications from the display.
Reset
is
effective when faulted only. This input terminal may be programmed to any of the functions listed in
). See the section titled
Alarms, Trips, and Troubleshooting on pg. 187
a listing of the faults that do not respond to a reset.
F
— The default terminal assignment is
Forward
run. As the default setting, this terminal provides a
forward run command. The
F
terminal is activated by connecting
CC
to this terminal (Sink mode). A
connection to
CC
provides a forward run command for the duration of the activation. This input
terminal may be programmed to any of the functions listed in
(see
R
— The default terminal assignment is
Reverse
run. As the default setting, this terminal provides a
reverse run command. The
R
terminal is activated by connecting
CC
to this terminal (Sink mode). A
connection to
CC
provides a forward run command for the duration of the activation. This input
terminal may be programmed to any of the functions listed in
(see
).
S1
— The default terminal assignment is
Preset Speed 1
. As the default setting, this terminal provides
a
Preset Speed 1
run command. The
S1
terminal is activated by connecting
CC
to this terminal (Sink
mode). A connection to
CC
provides a forward run command for the duration of the activation. The
Preset Speed 1
function is configured at
. This input terminal may be programmed to any of the
S2
— The default terminal assignment is
Preset Speed 2
. As the default setting, this terminal provides
a
Preset Speed 2
run command. The
S2
terminal is activated by connecting
CC
to this terminal (Sink
mode). A connection to
CC
provides a forward run command for the duration of the activation. The
Preset Speed 2
function is configured at
. This input terminal may be programmed to any of the
S3
— The default terminal assignment is
Preset Speed 3
. As the default setting, this terminal provides
a
Preset Speed 3
run command. The
S3
terminal is activated by connecting
CC
to this terminal (Sink
mode). A connection to
CC
provides a forward run command for the duration of the activation. The
Preset Speed 3
function is configured at
. This input terminal may be programmed to any of the
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......