96
WX9 ASD Installation and Operation Manual
V/f Five-Point 1 Voltage
Program
Special
V/f Five-Point Setting
The
V/f Five-Point 1 Voltage
establishes the percentage of the output voltage
that is to be associated with the frequency setting of
V/f Five-Point 1
Frequency
).
The
Current/Voltage Units Setup
setting will determine if the on-
screen selection for this parameter appears in the form of a Voltage (V) or as a
Percentage (%) of the ASD rating.
If using
Voltage
as a unit of measure and with no voltage correction (
Supply
Voltage Correction
(
) Disabled), the limit of the on-screen display value
for this parameter is 575.00 Volts.
If using
%
as a unit of measure and with no voltage correction (
Supply
Voltage Correction
(
) Disabled), the ASD output voltage will be the
percentage setting multiplied by the ASD-rated voltage.
See
V/f Five-Point 1 Frequency
(
) for additional information on this
setting
Direct Access Number — F191
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
No
Minimum — 0.0
Maximum — 100.0
Units — %
V/f Five-Point 2 Frequency
Program
Special
V/f Five-Point Setting
The
V/f Five-Point 2 Frequency
sets the frequency to be associated with the
V/f Five-Point 2 Voltage
(
F193)
.
See
V/f Five-Point 1 Frequency
(
F190)
for additional information on custom
V/f curves.
Direct Access Number — F192
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 299
Units — Hz
V/f Five-Point 2 Voltage
Program
Special
V/f Five-Point Setting
The
V/f Five-Point 2 Voltage
establishes the percentage of the output voltage
that is to be associated with the frequency setting of
V/f Five-Point 2
Frequency
).
The
Current/Voltage Units Setup
setting will determine if the
selection for this parameter appears in the form of a Voltage (V) or as a
Percentage (%) of the ASD rating.
The default setting is %.
See
V/f Five-Point 1 Frequency
(
F190)
for additional information on this
setting.
Direct Access Number — F193
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 100.0
Units — %
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......