WX9 ASD Installation and Operation Manual
135
Speed Loop Proportional Gain
Program
Feedback
PG Settings
This parameter sets the
Proportional Gain
(sensitivity) of the drive when
monitoring the
PG
signal to control speed. The larger the value entered here,
the more sensitive the drive is to changes in the received feedback and the
quicker it responds.
Direct Access Number — F376
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 3.2
Maximum — (ASD-Dependent)
Speed Loop Integral Gain (rad/second)
Program
Feedback
PG Settings
This parameter sets the response time of the
Speed Loop Integral Gain
. The
smaller the value here, the more pronounced (quicker) the effect of the integral
function.
Direct Access Number — F377
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.1
Maximum — (ASD-Dependent)
Units — Rad/Second
Motor Counter Data Selection
Program
Feedback
PG Settings
This parameter sets the pulses-per-revolution displayed on the Monitor screen
when using a shaft-mounted encoder for speed control. This setting is used for
display purposes only and does not affect the speed control of the system.
If zero is selected here, then the setting at
Electronic Gear Setting
)
determines the pulses-per-revolution to be displayed on the Monitor screen.
Settings:
0 —
F370
setting
1 — 256 pulses/revolution
2 — 512 pulses/revolution
3 — 1024 pulses/revolution
4 — 2048 pulses/revolution
5 — 4096 pulses/revolution
Direct Access Number — F378
Parameter Type —
Selection List
Factory Default —
Setting
Changeable During Run —
No
Speed Loop Parameter Ratio
Program
Feedback
PG Settings
Contact the TIC Customer Support Center for information on this parameter.
Direct Access Number — F379
Parameter Type —
Numerical
Factory Default —
1.00
Changeable During Run —
No
Minimum — 0.01
Maximum — 10.00
Units — Seconds
Preset Speed Operation Mode
Program
Frequency
Preset Speed Modes
This parameter Enables/Disables the
Use Speed
mode. When enabled, the
system uses all of the parameter settings of the
Preset Speed
being run.
Otherwise, only the frequency setting is used.
Settings:
0 — Disabled (Use Frequency Command Only)
1 — Enabled (Use Direction, Acc/Dec, V/f, and Torque)
Direct Access Number — F380
Parameter Type —
Selection List
Factory Default —
Disabled (Use
Frequency
Command Only)
Changeable During Run —
No
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......