WX9 ASD Installation and Operation Manual
95
Motor Overload Protection Level 4
Program
Motor
Motor Set 4
The
Motor Overload Protection Level 4
parameter specifies the motor
overload current level for
Motor Set 4
. This value is entered as either a
percentage of the full load rating of the ASD or as the FLA of the motor.
The unit of measurement for this parameter may be set to
Amps
(V/A) or it
may be set as a percentage of the ASD rating. The name-plated FLA of the
motor may be entered directly when
Amps
is selected as the unit of
measurement (see
Current/Voltage Units Setup
to change the display
unit).
Motor Overload Protection Level
settings
(1 – 4) will be displayed in
Amps
if the
EOI
display units are set to
V/A
rather than %.
Direct Access Number — F181
Parameter Type —
Numerical
Factory Default —
100.0
Changeable During Run —
Yes
Minimum — 10.0
Maximum — 100.0
Units — %
V/f Adjustment Coefficient
Program
Special
Special Parameters
This parameter may be used in the
Constant Torque
or the
Variable Torque
modes only and should be adjusted gradually to improve the application-
specific torque requirements. The
Manual Torque Boost 1
setting (
be adjusted to improve the low-frequency torque performance.
Note:
The
Torque Boost
setting should be adjusted gradually before
attempting performance corrections using this parameter.
Direct Access Number — F183
Parameter Type —
Numerical
Factory Default —
32
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
V/f Five-Point 1 Frequency
Program
Special
V/f Five-Point Setting
The
V/f Five-Point 1
Frequency
setting establishes the frequency that is to be
associated with the voltage setting of
V/f Five-Point 1 Voltage
).
The V/f Five-Point settings define a custom volts per hertz relationship for the
startup output of the ASD.
To enable this function, set the
V/f Pattern
) selection to
V/f Five-Point
Setting
.
V/f Curves
may be useful in starting high inertia loads such as rotary drum
vacuum filters.
Direct Access Number — F190
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 299
Units — Hz
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......