148
WX9 ASD Installation and Operation Manual
RX Gain
Program
Frequency
Speed Reference Setpoints
This parameter is used to fine-tune the gain of the
RX
input terminal when this
terminal is used as the control input while operating in the
Speed Control
or
the
Torque Control
mode.
This setting may be used to ensure that the 100% level of the input source (pot,
pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD
system.
This is accomplished by setting the input source to 100% and either increasing
or decreasing this setting to provide an output of 100% from the ASD.
Direct Access Number — F475
Parameter Type —
Numerical
Factory Default —
141
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 255
RX2 Bias
Program
Frequency
Speed Reference Setpoints
This parameter is used to fine-tune the bias of the
RX2
input terminal when this
terminal is used as the control input while operating in the
Speed Control
or
the
Torque Control
mode.
This setting may be used to ensure that the zero level of the input source (pot,
pressure transducer, flow meter, etc.) is also the zero level setting of the ASD
system.
This is accomplished by setting the input source to zero and either increasing or
decreasing this setting to provide a zero output from the ASD.
Direct Access Number — F476
Parameter Type —
Numerical
Factory Default —
99
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 255
RX2 Gain
Program
Frequency
Speed Reference Setpoints
This parameter is used to fine-tune the gain of the
RX2
input terminal when this
terminal is used as the control input while operating in the
Speed Control
or
the
Torque Control
mode.
This setting may be used to ensure that the 100% level of the input source (pot,
pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD
system.
This is accomplished by setting the input source to 100% and either increasing
or decreasing this setting to provide an output of 100% from the ASD.
Direct Access Number — F477
Parameter Type —
Numerical
Factory Default —
141
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 255
Exciting Strengthening Coefficient
Program
Special
Special Parameters
This parameter determines the rate at which the excitation current is allowed to
go from zero to saturation and is enabled at
Direct Access Number — F480
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
Selection for Over Exciting Cooperation
Program
Special
Special Parameters
This parameter determines the method used to control the rate that the
excitation current is allowed to reach saturation. If
Effective
is selected, the
preset
Torque
Control
or
Speed
Control
settings will determine the rate that
the motor reaches excitation saturation.
Settings:
0 — Effective
1 — Applied by F480
Direct Access Number — F481
Parameter Type —
Selection List
Factory Default —
Effective
Changeable During Run —
Yes
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......