110
WX9 ASD Installation and Operation Manual
BIN Reference Point 1
Program
Torque
Setpoints
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the direction, gain, and bias of the
BIN
binary input
terminals when these
terminals are used as the control input while operating in
the
Speed
Control
or the
Torque Control
mode.
The discrete input terminals of the
Terminal Board
are used as the
BIN
terminals.
BIN Speed Control Setup
Perform the following setup to allow the system to receive
Speed
control input
at the
BIN
terminals:
•
Program
Fundamental
Standard Mode Selection
Frequency
Mode 1
Binary/BCD
.
•
Program
Fundamental
Standard Mode Selection
Command
Mode Selection
Terminal Board
.
•
Program
Terminal
Input Terminals
; select and set the desired
discrete input terminals to
Binary Bit
(s)
0 – 7
(or 0 – MSB). The binary terminal input byte will control the
speed of the motor.
•
Program
Terminal
Input Terminals
; select and set a
discrete input terminal to
Binary Data Write
. Activation of the
Binary Data Write
terminal will transfer the status of the
Binary
Bit
(s)
0-7
(or 0-MSB) to the control board for speed control.
•
Set
BIN Point 1 Frequency
(
).
•
Set the
BIN
value (% of 255
D
) (
BIN Reference
Point 1
.
Note:
255
D
is the decimal equivalent of the 8-bit BIN word with
all input terminals set to one (255 decimal = 11111111
binary).
•
Set
BIN Point 2 Frequency
(
)
•
Set the
BIN
value (% of 255
D
) (
BIN Reference
Point 2
.
•
Provide a
Run
command (F and/or R).
Once set, as the
BIN
signal changes are transferred to the control board, the
directional information, the output frequency, or the output torque of the drive
will vary in accordance with the above settings.
This parameter sets
BIN Reference Point 1
(direction/torque/frequency) and is
entered as 0 to 100% of the
BIN
binary input byte 11111111 (255
D
) or the
binary bit(s) 0 - MSB.
Direct Access Number — F228
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 100.00
Units — %
Frequency Settings
Torque Settings
BIN Point 1 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the direction, gain, and bias of the
BIN
binary input
terminals when these terminals are used as the control input while operating in
the
Speed Control
mode.
This parameter sets
BIN Point 1 Frequency
and is the frequency that is
associated with the setting of
See
BIN Reference Point 1
(
)
for additional information on this setting.
Direct Access Number — F229
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — - (Maximum Freq. (
Maximum — + (Maximum Freq. (
))
Units — Hz
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......