WX9 ASD Installation and Operation Manual
67
4. Adjust Accel/Decel Automatically?
When enabled, the
WX9 ASD
adjusts the acceleration
and deceleration rates according to the applied load.
The acceleration and deceleration times range from
12.5 to 800% of the programmed values [e.g.,
Acceleration Time 1
(
) and Deceleration Time 1
) adjusted for the actual Accel/Decel times used].
Note:
The motor and the load must be connected prior
to selecting
Automatic Acc/Dec
.
Settings:
0 — Disabled
1 — Enabled
5. Volts Per Hertz Setting
This function establishes the relationship between the
output voltage and the output frequency of the ASD.
Settings:
0 — Constant Torque
1 — Variable Torque
2 — Automatic Torque Boost
3 — Sensorless Vector Control (speed)
4 — Automatic Torque Boost with Automatic Energy Saving
5 — Sensorless Vector Control (speed) with Automatic Energy Saving
6 — V/f 5-Point Setting (opens 5-point setting screen)
7 — Sensorless Vector Control (speed/torque switching)
8 — PG Feedback Vector Control (speed/torque switching)
9 — PG Feedback Vector Control (speed/position switching)
6. Motor Current Rating
This parameter allows the user to input the full-load
amperage (FLA) of the motor. This value is used by
the
WX9 ASD
to determine the motor overload
protection setting for the motor. The value is found on
the nameplate of the motor.
Deceleration Time
Acceleration Time
Accelerati
on Time
Decelerati
on Time
If
Automatic Acc/Dec
is not enabled, the
Acceleration
screen
will appear followed by the
Deceleration
screen as shown below.
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......