72
WX9 ASD Installation and Operation Manual
Type Reset
Program
Utilities
Type Reset
This feature assists the user when performing fault analysis or by allowing a
quick system setup change when required. Performing a
Type Reset
results in
one of the following user-selected post-reset configurations.
Settings:
0 — None
1 — 50 Hz Setting
2 — 60 Hz Setting
3 — Reset to Factory Settings
4 — Clear Past Trips
5 — Clear Run Timer
6 — Initialize Typeform
7 — Save User Settings
8 — Restore User Settings
9 — Reset EOI to Factory Settings
Note:
*User settings that are stored in the memory of the EOI are not
saved via the
Save User Parameters
selection. The unsaved
functions include the
EOI Option Setups
, (Utility Parameters
Display Units
, and (Monitor Setup
)
Scrolling Monitor
Select
.
Direct Access Number — F007
Parameter Type —
Selection List
Factory Default —
None
Changeable During Run —
No
Acceleration Time 1
Program
Fundamental
Acc/Dec 1 Settings
Program
Special
Acc/Dec (1 - 4) Settings
This parameter specifies the time in seconds for the drive to go from 0.0 Hz to
the
Maximum Frequency
)
for the
Acceleration 1 Profile
. The
Acceleration/Deceleration (Acc/Dec)
pattern may be set using
minimum
Acc/Dec
time may be set using
.
Note:
An acceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Automatic Acceleration/Deceleration
and
Stall
settings
may
lengthen the acceleration time.
Acceleration
The acceleration rate of a motor is determined by several factors: applied
power, applied load, and the physical properties of the motor (winding
parameters, motor size, etc.). The ASD will control the first of these factors:
input power. The settings of the ASD control the frequency and amplitude of
the applied voltage to the motor.
Under most operating conditions, as the output frequency of the drive goes up
so does the output voltage (linear acceleration). The ASD has the ability to
modify the relationship between frequency and voltage automatically to
produce smoother operation or increased (starting) torque.
Direct Access Number — F009
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum —
Maximum — 6000
Units — Seconds
Reset
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......