WX9 ASD Installation and Operation Manual
Over-Voltage Limit Operation
Program
Protection
Stall
This parameter Enables/Disables the
Over-Voltage Stall
function. When
enabled, this function causes the drive to extend the deceleration time when the
DC bus voltage increases due to transient voltage spikes, regeneration, supply
voltage out of specification, etc., in an attempt to reduce the bus voltage.
An
Over-Voltage Stall
increases the output frequency of the ASD during
deceleration for a specified time in an attempt to prevent an
Over-Voltage
Trip
.
If the over-voltage threshold level setting of
is exceeded for over 4 mS, an
Over-Voltage Trip
will be incurred.
Parameter
(Power Running Stall Continuous Trip Detection Time) setting
may affect the performance of this setting.
Note:
This setting may increase deceleration times.
Settings:
0 — Enabled
1 — Disabled
2 — Enabled (Forced Shorted Deceleration)
Direct Access Number — F305
Parameter Type —
Selection List
Factory Default —
Enabled
Changeable During Run —
Yes
Base Frequency Voltage 1
Program
Fundamental
Motor Set 1
Program
Motor
Motor Set 1
This parameter sets the maximum value of the output voltage of the drive. The
Motor 1 Maximum Output Voltage
is the
Motor
1
output voltage at the
Base
Frequency
). Regardless of the programmed value, the output voltage
cannot be higher than the input voltage.
The actual output voltage will be influenced by the input voltage of the ASD
and the
Supply Voltage Compensation
This parameter is used only when the parameters for
Motor Set 1
are
configured and selected.
Motor Set 1
may be selected by a properly configured
Direct Access Number — F306
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 600.0
Units — Volts
Supply Voltage Correction
Program
Protection
Base Frequency Voltage
This parameter Enables/Disables the
Voltage Compensation
function.
When
Enabled
, this function provides an output waveform adjustment that
compensates for changes in the input voltage.
Settings:
0 — Disabled
1 — Supply Voltage Compensation
2 — Output Voltage Limitation
3 — Supply Voltage Compensation with Output Voltage Limitation
Direct Access Number — F307
Parameter Type —
Selection List
Factory Default —
Supply Voltage
Compensation
Changeable During Run —
No
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......