158
WX9 ASD Installation and Operation Manual
Output Phase Failure Detection
Program
Protection
Phase Loss
This parameter Enables/Disables the monitoring of each phase of the three-
phase output signal (U, V, or W) of the ASD. If either line is missing, inactive,
or not of the specified level, the ASD incurs a trip.
Note:
Autotune checks for phase failures regardless of this setting.
Settings:
0 — Disabled
1 — Enabled
Direct Access Number — F605
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
No
Overload Reduction Start Frequency
Program
Protection
Overload
This parameter is primarily used with V/f motors. It is used to reduce the
starting frequency at which the
Overload Reduction
function begins and is
useful during extremely low-speed motor operations.
During very low-speed operation, the cooling efficiency of the motor decreases.
Lowering the start frequency of the
Overload Reduction
function aides in
minimizing the generated heat and precluding an
Overload
trip.
This function is useful in loads such as fans, pumps, and blowers that have the
square reduction torque characteristic.
Set
to the desired
Overload Time Limit
.
Direct Access Number — F606
Parameter Type —
Numerical
Factory Default —
6.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 30.00
Units — Hz
Motor 150% Overload Time Limit
Program
Protection
Overload
This parameter establishes a time that the motor may operate at 150% of its
rated current before tripping. This setting applies the time/150% reference to
the individual settings of each motor (e.g., this setting references 150% of the
setting for the
1 motor
).
The unit will trip sooner than the time entered here if the overload is greater
than 150%.
Direct Access Number — F607
Parameter Type —
Numerical
Factory Default —
600
Changeable During Run —
Yes
Minimum — 10
Maximum — 2400
Units — Seconds
Suppression of Inrush Current Timing
Program
Protection
Special Protection Parameters
The startup inrush current may be suppressed. This parameter Enables/Disables
the inrush current suppression function.
Settings:
0 — Disabled
1 — Enabled
Direct Access Number — F609
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
No
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......