WX9 ASD Installation and Operation Manual
Startup Wizard Requirements
The
Startup Wizard
assists the user with the initial configuration of the
WX9 ASD
by querying the
user for information on the frequently used ASD control settings and system operational specifications.
The WX9 ASD may also be setup by directly accessing each of the settings via the
Program
menu or
the
Direct Access Number
for each item (see the section titled
Direct Access Parameter Information on
for specifics on each parameter). Application-specific settings may still be required upon
completion.
The
Startup Wizard
is launched from the
Program
menu.
Select the input power specifications or click
Manually Configure-Finish
to exit.
Input the required information into the following screens to complete the
Startup Wizard
. Click
Next
or
Finish
after each window.
Next
opens the next
Startup Wizard
window.
Finish
returns the system
to the
1. Voltage and Frequency Rating of the Motor
Motors are designed and manufactured for operation
within a specific voltage and frequency range. The
voltage and frequency specifications for a given motor
may be found on the nameplate of the motor.
Settings:
2 — 380v, 50Hz
3 — 460v, 60Hz
2. Upper-Limit Frequency
This parameter sets the highest frequency that the
WX9 ASD
will accept as a frequency command or
frequency setpoint. The WX9 ASD may output
frequencies greater than the
Upper-Limit Frequency
(but less than the Maximum Frequency) when
operating in the
PID Control
mode,
Torque Control
mode, or the
Vector Control
modes (sensorless or
feedback).
3. Lower-Limit Frequency
This parameter sets the lowest frequency that the
WX9
ASD
will accept as a frequency command or
frequency setpoint. The WX9 ASD will output
frequencies lower than the
Lower-Limit Frequency
when accelerating to the lower limit or decelerating to
a stop. Frequencies below the
Lower Limit
may also
be output when operating in the
PID Control
mode,
Torque Control
mode, or the
Vector Control
modes (sensorless or feedback).
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......