WX9 ASD Installation and Operation Manual
171
Low Output Disable Feedback Level
Program
Motor
Low Output Disable Function
The
Low Output Disable Feedback Level
sets a frequency level that the ASD
output must drop below in order for the
Restart Delay Timer
to start.
Direct Access Number — F736
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz
Low Output Disable Restart Delay Time
Program
Motor
Low Output Disable Function
The
Low Output Disable Restart Delay Time
sets the time that must pass
before normal ASD operation resumes (all standard ASD requirements must be
met).
Direct Access Number — F737
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
Baud Rate (TTL)
Program
Communications
Communication Settings
This parameter plays a role in the setup of the communications network by
establishing the
Baud Rate
of the communications link.
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the settings of the ASD.
Note:
Changes made to this parameter require that the power be cycled
(off then on) for the changes to take effect.
Settings:
0 — 1200
1 — 2400
2 — 4800
3 — 9600
Direct Access Number — F800
Parameter Type —
Selection List
Factory Default —
9600
Changeable During Run —
Yes
Minimum — 1200
Maximum — 9600
Units — BPS
Parity
Program
Communications
Communication Settings
This parameter plays a role in the setup of the communications network by
establishing the
Parity
setting of the communications link.
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the settings of the ASD.
Note:
Changes made to this parameter require that the power be cycled
(off then on) for the changes to take effect.
Settings:
0 — No Parity
1 — Even Parity
2 — Odd Parity
Direct Access Number — F801
Parameter Type —
Selection List
Factory Default —
Even Parity
Changeable During Run —
Yes
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......