156
WX9 ASD Installation and Operation Manual
Deceleration Time 4
Program
Special
Acc/Dec (1 - 4) Settings
This parameter specifies the time for the drive to go from the
Maximum
Frequency
to 0.0 Hz for the
Deceleration (Dec) 4 Profile
. The
Acceleration/
Deceleration (Acc/Dec)
pattern may be set using
. The minimum
Acc/Dec
time may be set using
Note:
A deceleration time that is shorter than the load will allow may
cause nuisance tripping and mechanical stress to loads.
Automatic Acceleration/Deceleration
,
Stall
, and
Ridethrough
settings
may lengthen the deceleration time.
Direct Access Number — F515
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 6000.00
Units — Seconds
Acceleration/Deceleration Pattern 4
Program
Special
Acc/Dec (1 - 4) Settings
This parameter enables a user-selected preprogrammed output profile that
controls the acceleration and deceleration pattern for the
Acceleration/
Deceleration (Acc/Dec) 4
parameter.
Settings:
0 — Linear
1 — S-Pattern 1
2 — S-Pattern 2
Direct Access Number — F516
Parameter Type —
Selection List
Factory Default —
Linear
Changeable During Run —
Yes
Acceleration/Deceleration Switching Frequency 3
Program
Special
Acc/Dec Special
This parameter sets the frequency at which the acceleration control is switched
from the
Acceleration (Acc) 3
Profile
to the
Acceleration (Acc) 4
Profile
during a multiple-profile configuration.
Direct Access Number — F517
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz
Motor Overload Protection Level 1
Program
Fundamental
Motor Set 1
Program
Motor
Motor Set 1
The
Motor Overload Protection Level 1
parameter specifies the motor
overload current level for
Motor Set 1
. This value is entered as either a
percentage of the full load rating of the ASD or as the FLA of the motor.
The unit of measurement for this parameter may be set to
Amps
or it may be set
as a percentage of the ASD rating. The nameplated FLA of the motor may be
entered directly when
Amps
is selected as the unit of measurement (see
Current/Voltage Units Setup
(
) to change the display unit).
Motor Overload Protection Level
settings
(1 – 4) will be displayed in
Amps
if the
EOI
display units are set to
V/A
rather than
%
.
Direct Access Number — F600
Parameter Type —
Numerical
Factory Default —
100.0
Changeable During Run —
Yes
Minimum — 10.0
Maximum — 100.0
Units — %
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......